DeviceNet Objects 71
Services
1
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object 
for more information.
4
Boot Program
Vendor-specific, indicates that the boot program is 
running. The Main Application must be corrupt or 
missing.
5 - 7
Vendor-specific, not implemented
8
Minor Recoverable 
Fault
Not implemented
9
Minor Unrecoverable 
Fault
Not implemented
10 Major
Recoverable
Fault
Set when the module detects a major problem that the 
user may be able to recover from. The Module Status 
LED will flash red. An example of this condition is when 
the boot program is running.
11
Major Unrecoverable 
Fault
Set when there is a module status fault (Module Status 
LED is solid red). 
12 - 15
Reserved, set to 0
Table C.3 Identity Object Services
Service 
Code
Class/Instance Usage
Name
01
h
Instance
Get_Attributes_All
05
h
Instance
Reset
0E
h
Instance
Get_Attribute_Single
10
h
Instance
Set_Attribute_Single
1
Table C.2 Identity Object Status
Bit
Name
Description