Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual
Page 65
 
Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011
DeviceNet Information 65
To configure the Sharing Status
Parameters 65 to 128 (Sharing Status group) are used to enter the share status 
information. 
Follow these guidelines when configuring the Share Option parameter.
• If the XM-440 is the primary master of an XM measurement module,
then the Share Option parameter for the corresponding node address 
must be set to "primary." 
• If another master/scanner is the primary master of the XM
measurement module, and the XM-440 is to share the XM measurement 
module, then the Share Option parameter for the corresponding node 
address must be set to "shared." 
Note that a generic master/scanner must always be the primary master 
and the XM-440 must always share the slave. This is because of the way 
the Scanner applet works. If the Share Option parameter is set to 
"primary," the Scanner applet would not know that a primary master has 
been selected for the XM measurement module (because the Scanner 
applet was not used to configure the XM-440). So the Scanner applet 
would not be able to enable the shared inputs function when adding the 
XM measurement module to the generic master/scanner’s scan list. And 
both the generic master/scanner and the XM-440 would try to be the 
primary master for the XM measurement module. 
IMPORTANT
There can be only one primary master of a slave. And a 
slave must have a primary master before it can be shared 
with another master/scanner.