32 Installing the XM-440 Master Relay Module
Connecting the Remote Relay Reset Signal
If you set the module relay to latching and the relay activates, the relay stays 
activated even when the condition that caused the alarm has ended. The 
remote relay reset signal enables you to reset your module relay remotely after 
you have corrected the alarm condition. This includes latched relays in the 
Expansion Relay module when it is attached to the XM-440..
Wire the Remote Relay Reset Signal to the terminal base unit as shown in 
Figure 2.13.
Figure 2.13 Remote Relay Reset Signal Connection
TIP
You can discretely reset a relay using the serial or remote 
configuration tool.
TIP
If you set a measurement module relay to latching, make 
sure that any linked relays, such as relays in an XM-440 
module, are not configured as latching. When both relays 
are set to latching, the relay in each module will have to be 
independently reset when necessary. 
ATTENTION
The Switch Input circuits are electrically isolated from 
other circuits. It is recommended that the Switch RTN 
signal be grounded at a signal point. Connect the Switch 
RTN signal to the XM terminal base (Chassis terminal) or 
directly to the DIN rail, or ground the signal at the switch 
or other equipment that is wired to the switch. 
Momentary
Switch