Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual
Page 46
 
Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011
46 Configuration Parameters
Controls whether the relay must be explicitly reset 
after the alarm subsides.
Activation Delay
Enter the length of time for which the relay 
activation logic (Activate relay when parameter) 
must be true before the relay is activated. 
Enter a value from 0 to 25.5 seconds, 
adjustable in increments of 0.1 
seconds.
Default is 1 second
Sets the alarm conditions that will cause the relay to 
activate. You can select more than one.
• Normal - The current measurement is not in
within excess of any alarm thresholds.
• Alert - The current measurement is in excess of
the alarm level threshold(s) but not in excess of the 
danger level threshold(s).
• Danger - The current measurement is in excess of
the danger level threshold(s).
• Disarm-The alarm is disabled or the device is in
Program mode.
• Xdcr (Transducer) Fault - A transducer fault is
detected on the associated transducer.
• Module Fault - Hardware or firmware failure, or
an error has been detected and is preventing 
proper operation of the device.
• Tacho Fault - A required tachometer signal has
not been detected. Note that there is no 
transducer fault either.
• Unknown - The current alarm status cannot be
determined. This is useful when the XM-440 loses 
its communication link and can no longer receive 
the actual alarm status values.
Options: Normal
Danger
Xdcr Fault
Tacho Fault
Alert
Disarm
Module Fault
Unknown
Check to enable.
Clear to disable.
Relay Installed
 
Indicates whether the relay is a physical relay on a 
module or a virtual relay. If the relay is a physical 
relay, then you can set the Failsafe parameter.
If the relay is a virtual relay, the Failsafe parameter 
is not used or it is disabled.
Relay Parameters
Parameter Name
Description
Options/Comments
XM Configuration 
Utility
EDS File
Latching
Latching 
Option
XM Configuration 
Utility
EDS File
Check means 
latching (relay must 
be explicitly reset)
Latching
Clear means 
non-latching (relay 
is reset once the 
alarm condition has 
passed)
Nonlatching
XM Configuration 
Utility
EDS File
Alarm Status to 
Activate On
Alarm Levels
XM Configuration 
Utility
EDS File
Check = Physical 
Relay
Installed = 
Physical Relay
Clear = Virtual Relay Not Installed =
Virtual Relay