Class attributes – Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual
Page 77
 
Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011
DeviceNet Objects 77
Parameter instances 513-524 are for the Group feature. There are four groups 
with three parameters per group. The first parameter specifies the slave nodes 
that are members of the Group. The second parameter specifies the Relay 
Object instances that are inputs for the Group’s trigger. The third parameter 
determines whether any or all of the Relay inputs must be activated in order 
for a Group trigger to occur. When the Group trigger occurs, a trigger event is 
sent to all of the member nodes.
Class Attributes
Table C.14 Parameter Object Class Attributes
Attr ID
Access 
Rule
Name Data
Type
Description
Semantics
2
Get
Max Instance
UINT
Maximum instance 
number of an object in 
this class.
Total number of parameter 
object instances.
8
Get
Parameter Class 
Descriptor
WORD
Bits that describe the 
parameter.
Bit 0 Supports Parameter 
Instances
Bit 1 Supports Full Attrib.
Bit 2 Must do non-volatile store
Bit 3 Params in non-volatile
9
Get
Config. 
Assembly 
Instance
UINT
Set to 0