Grounding Requirements
Use these grounding requirements to ensure safe electrical operating 
circumstances, and to help avoid potential emi and ground noise that can cause 
unfavorable operating conditions for your XM system.
DIN Rail Grounding
The XM modules make a chassis ground connection through the DIN rail. 
The DIN rail must be connected to a ground bus or grounding electrode 
conductor using 8 AWG or 1 inch copper braid. See Figure 2.2.
Use zinc-plated, yellow-chromated steel DIN rail (Allen-Bradley part no. 
199-DR1 or 199-DR4) or equivalent to assure proper grounding. Using other 
DIN rail materials (e.g. aluminum, plastic, etc.), which can corrode, oxidize, or 
are poor conductors can result in improper or intermittent platform 
grounding.