Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual
Page 67
 
Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011
DeviceNet Information 67
• The ADR scanner saves and restores only the configuration parameters
contained in the module’s EDS file. Some XM parameters are not 
included in the EDS file because they are not supported by either the 
EDS specification or the tools that read the EDS files, for example 
RSNetWorx for DeviceNet. These configuration parameters will not be 
restored with ADR.
Below is a list of the configuration parameters that are not included in 
the EDS file and can not be saved or restored with ADR.
– Channel Name 
– Tachometer Name
– Alarm Name
– Relay Name
– All Triggered Trend related parameters 
– All SU/CD Trend related parameters 
– Custom Assembly structure 
• The ADR and trigger group functions cannot be used together. A
module can have only one primary master so a module cannot be both 
configured for ADR and included in a trigger group. The ADR scanner 
must be the primary master for the modules configured for ADR. The 
XM-440 Master Relay module must be the primary master for modules 
included in a trigger group.