Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual
Page 49
 
Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011
Configuration Parameters 49
• The group trigger will work only with XM measurement modules
running revision 4 or later firmware.
IMPORTANT
The Group Triggers parameters are not included in the 
EDS file and cannot be edited using generic configuration 
tools such as RSNetWorx for DeviceNet. 
Group Trigger Parameters
Parameter Name
Description
Values/Comments
Group List
Sets the trigger group to be configured.
You can create up to four trigger 
groups for each XM-440 module.
Node Address
The node address of the XM measurement module in 
the selected trigger group.
The XM measurement module must be 
added to the XM Network Node List 
before it can be added to the trigger 
group. Refer to XM Network Node List 
on page 41. 
Module Type
The type of XM measurement module at this node 
address.
Trigger when...
Determines whether the group trigger occurs when 
any or all of the selected relays are activated.
Important: When this parameter is set to "Any," the 
trigger event will be sent to the group on the initial 
activation of any relay in the group. Subsequent 
activations of relays in the group will not generate 
subsequent trigger events. A subsequent trigger 
event will not be sent until all of the relays in the 
group are deactivated.
Relay 1–12
Sets the XM-440 relays to use as the trigger for the 
selected trigger group.
The relay must be enabled before it 
can be used as a trigger. Refer 
to Relay Parameters on page 45.