38 MP-Series Heavy Duty Electric Cylinders

Rockwell Automation Publication MPAI-IN001E-EN-P - March 2012

7. Click Yes to begin tuning the electric cylinder.

Tuning is complete when the Tune Servo dialog

box opens.

8. Click OK to exit Tuning.

The Tune Results dialog box opens.

9. Click OK if you are satisfied with the tuning results; otherwise, continue with

Calculate

and Configure the Loop Gain

.

Calculate and Configure the Loop Gain

Calculate a position loop bandwidth based on the actual measured inertia values from the Tune

Results dialog box.
In this example, the Tune Results dialog box shows a default Position Loop Bandwidth of

45.14153 Hz, and a Load Inertia Ratio of 6.8707952.

1. Calculate the Corrected Position Bandwidth.

Corrected Position Loop Bandwidth = (Initial Position Loop Bandwidth Result/(Initial

Load Inertia Ratio Result +1)
For example, 5.73532 = 45.14153/7.8707952