Remark <comment, Rtdataserveroff, Rtdataserveron [/quiet] [/netdde – Rockwell Automation 9301 Series RSView32 Users Guide User Manual
Page 672

A–52
RSView32 User’s Guide
Remark
Remark <comment>
Writes a text string to an activity log file, which is useful for operators
to store comments.
<comment>
A string up to 132 characters long. The string can
contain any characters, including spaces. Enclose the
exclamation mark (!) and the semi–colon (;) in single
or double quotes.
To log comments, the Remarks category must be selected in the
Activity Log Setup editor.
RTDataServer
Off
RTDataServerOff
Stops running the RSView32 real-time data server.
RTDataServerOn
RTDataServerOn [/Quiet] [/NetDDE]
The RSView32 OPC or DDE server is also known as the real-time
data server. This command runs the RSView32 real-time data server,
allowing OPC and DDE client applications to read (but not write) tag
values.
To enable writes, use the RTDataWriteEnable command.
[/Quiet]
Makes RSView32 use the current Remote Users
accessibility setting in the Windows Registry. Without
this parameter or if the setting is not configured
correctly, RSView32 displays a dialog box that allows
you to specify the setting when you issue the
command.
[/NetDDE]
Enables RSView32 as a NetDDE server to remote
DDE clients. If the real-time data server is already
running, this parameter is ignored.