System tags, Alarms, Appendix b – Rockwell Automation 9301 Series RSView32 Users Guide User Manual
Page 682

B–1
Appendix
B
System tags
System tags are preconfigured tags created by RSView32
™
. Use system
tags for read–only applications in your project.
Alarms
The following tags display alarm information:
Tag Name
Type
Displays information about
system\AlarmBanner
String
The most recent, most severe alarm. If an
alarm of an equal or higher severity occurs,
it replaces the first alarm, even if the
previous alarm has not been acknowledged.
system\AlarmMostRecentDate
String
The date of the most recent, most severe
alarm.
system\AlarmMostRecentLabel
String
The threshold label of the tag of the most
recent, most severe alarm.
system\AlarmMostRecentSeverity
Analog
The severity of the most recent, most
severe alarm.
system\AlarmMostRecentTagDesc
String
The description of the tag of the most
recent, most severe alarm.
system\AlarmMostRecentTagname
String
The name of the tag of the most recent,
most severe alarm.
system\AlarmMostRecentTime
String
The time of the most recent, most severe
alarm.
system\AlarmMostRecentUnits
String
The units of the most recent, most severe
alarm.
system\AlarmStatus
String
The number of unacknowledged and
suppressed alarms.