Addressing syntax for Allen–Bradley programmable controllers
D–15
SLC 5 binary files: optional syntax
Fnnn/bbbb
F
File type
B = Binary
nnn
(optional)
File number: 3, 9 – 255 decimal
For direct driver communication, the default file
number 3 is used if the file number is absent.
bbbb
Bit offset from start of file: 0 – 4095 decimal
Example: B3/3999
SLC 5 timer, counter, and control files
Fnnn:eee.MNE/bb
F
File type:
T = Timer
C = Counter
R = Control
nnn
(optional)
File number:
Timer: 4, 9 – 255 decimal
Counter: 5, 9 – 255 decimal
Control: 6, 9 – 255 decimal
For direct driver communication, timer, counter,
and control file types use the default file number
if the file number is absent. The default numbers
are 4 (timer), 5 (counter), and 6 (control).
eee
Element number: 0 – 255 decimal
MNE
Member mnemonic (see mnemonic tables
starting on page D-30)
bb
(optional)
Bit number: 0 – 15 decimal
Applies to analog members only.
Example: R67:123.EN