Rockwell Automation 9301 Series RSView32 Users Guide User Manual
Page 745

Station addressing for nodes connecting to Allen–Bradley devices
E–11
if connected on a KA, type: mKA:n
where m is the pushwheel number (1 to 4) on the KA and n is the
KA channel number (2 or 3).
station_address
is one of the following:
Remote Network
Station Address
Valid Entries
DH
lll
local station address
0 – 376 (octal)
DH+
ll
local station address
0 – 77 (octal)
DH bridged by a
1785–KA module
ll.sss
ll
local bridge address
sss
station address on remote DH+
0 – 77 (octal)
0 – 376 (octal)
DH+ bridged by
two 1785–KA
modules
ll.rrr.ss
ll
local bridge address
rrr
remote bridge address
ss
station address on remote DH+
or
ll.rss
ll
local bridge address
rss
combined remote bridge address and
remote station address
The address ll.rss is an offlink address that is
shortened by combining the remote bridge and
remote station addresses into one three–digit
number. The system reads only the first digit of
the remote bridge address, and adds the two–digit
remote station address to produce a shorter
address that still points to the same node.
0 – 77 (octal)
0 – 376 (octal)
0 – 77 (octal)
0 – 77 (octal)
0 – 376 (octal)