SP200 AC Drive Quick Start Guide
Technical Specifications
Control Inputs
• Rated voltage: 10 VDC to 24 VDC (±10%)
• Load (each): 10 mA minimum, 20 mA maximum
• Maximum allowable off-state leakage current: 1.5 V / 2.0 mA
Speed Reference Input
• Analog input impedance: 0 to 10 V:
≥
100 k
Ω
4 to 20 mA input: ~250
Ω
Relay Output
• Rated current and voltage: 0.5 A maximum at 125 VAC
1.0 A maximum at 30 VDC
Operating Performance
• Input frequency resolution: 0.4% analog, 0.1 Hz digital
• Output frequency resolution: 0.1%
• Output voltage regulation: 3%
• Power dip control ride through time: 100 msec minimum
Ambient Conditions
• Operating temperature: 0 to 50
°
C (32
°
F to 122
°
F)
• Storage temperature: -40
°
C to 85
°
C (-40
°
F to 185
°
F)
• Humidity: 0 to 95% non-condensing
• Elevation: 1000 meters (3300 ft) maximum without derating. For every 91.4 meters
(300 ft) above 1000 meters, derate the current by 1%. Above 3000 meters,
(10,000 ft), consult your Reliance Electric Sales Office.
AC Input
Voltage
1
1
The input voltage range has a tolerance of ±10%, 47 to 63 Hz.
AC
Output
Voltage
HP
Input
Current
(Amps)
Output
Current
(Amps)
Fuse
Rating
2
(Amps)
2
Recommended fuse type: UL Class J or CC, 600 V, time delay.
Circuit
Breaker
Rating
3
(A)
3
Device must meet UL 489 for UL purposes.
Typical
Power
Loss (W)
100-120,
1-phase
230,
3-phase
0.5
1.0
1.5
9.4
17.2
24.6
2.3
4.2
6.0
15 or 16
30
40
15
30
40
25
45
70
200-240,
1-phase
230,
3-phase
0.5
1.0
1.5
2.0
4.7
8.6
12.3
14.3
2.3
4.2
6.0
7.0
10
15 or 16
20
25
10
15
20
25
25
45
70
75
200-240,
3-phase
230,
3-phase
0.5
1.0
2.0
2.7
5.0
8.3
2.3
4.2
7.0
6
10
15 or 16
5
7
15
25
40
70
380-460,
3-phase
460,
3-phase
0.5
1.0
2.0
1.5
2.4
4.1
1.3
2.0
3.5
3 or 4
6
10
3
4
7
25
30
50