3 programming control module response, Control module configuration – Banner A-GAGE High-Resolution MINI-ARRAY Series User Manual

Page 21

Advertising
background image

21

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

P/N 64118 rev. B

Control Module Configuration

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

To accommodate parts or components that will move through

the array, blanking may be manually adjusted for one or more

individual beam channels. After using the System software to

specify blanking, select ‘Edit’ from the Alignment screen; the

Diagnostics Indicator will continue to show the letter ‘b’ and a

grid will appear on the computer screen (Figure 5-8). The

beams are numbered from the sensors’ cabled ends, with the

beam closest to the cable being beam #1. To set the blanking

fields, ‘click’ each grid box representing a beam you wish to

blank.

Clicking again on a blanked beam channel will remove the

blanking specification. Rows of channels can be selected or

cleared of the blanking specification by placing the cursor

directly to the left of the row to be selected and clicking the

mouse; the row should be highlighted. Select the Blank

Selected (to accept the blanking status) or Clear Selected (to

reject the blanking status) option. To leave Alignment mode,

select ‘OK’. Both the control module and the receiver will

indicate a clear condition (green Align indicator ON) and the

Diagnostics Indicator will show ‘A.’. When the System is ready

for operation and configured for beams to be blanked, the

period on the Diagnostics Indicator will remain lit, showing ‘—.

(see Figure 5-4).

Figure 5-8. Edit channel blank state screen, showing beam #22 and

beams #35-42 blanked; beams #65-80 are highlighted,

ready to be selected for blanking

5.3 Programming Control Module Response

The Parameter Setup File (PSF) Configuration routine (see Figure 5-9) is used to

configure the control module for a specific application. Access the PSF Configuration

screen (after performing the Ping routine to select a control module, section 5.1.1) by

selecting Edit PSF (F4) from the MINI-ARRAY menu. The Edit PSF process may also

be performed with no control module selected, to configure and save a PSF for

multiple control modules. In such a case, some fields on the PSF Configuration screen

will not be accessible.

The process of configuring the control module involves selecting among options for

each of the parameters listed in this section, including serial communication, control

mode, scanning method, scan analysis mode, serial transmission, and analog/discrete

outputs. The resulting combination of options causes the control module to react as

required for the application, to changes in the light screen.

The configuration process produces a Parameter Setup File (PSF). PSF files may be

saved and retrieved as computer files via the File Save PSF and File Retrieve PSF

commands (see section 5.4.5). Once configured, a PSF may be sent to the control

module via the Send PSF command. Likewise, the PSF currently loaded into the

control module may be displayed by using the Upload PSF command.

Advertising