Limit, On/off, On delay – Banner MAXI-AMP Series User Manual

Page 6: Off delay, On & off delay, One-shot, Delayed one-shot, Repeat cycle, Ac latch, Dc latch

Advertising
background image

LIMIT:

The output of the LIMIT function follows the action of the input, as it does with the ON/OFF function. However,

an input signal which is longer than the adjustable LIMIT ("HOLD") time will turn the output "off". Removing the input signal
resets the timer. This function is sometimes called "TIME LIMITED ON/OFF", and is useful for energy conservation.
Grounding pin #9 cancels the output. Lifting the inhibit restarts the LIMIT timer, if an input signal is present.

ON/OFF:

ON/OFF operation does not involve timing. The output simply follows the action of the input signal.

Grounding pin #9 (AUXILIARY) turns the output "off", regardless of the state of the input signal. This may be accomplished
by closing a switch or relay contact between pins #9 and #1 (common), or by connecting an open collector NPN (current sinking)
output of any external dc device directly to pin #9. NOTE: connect the COMMON of any external dc device to pin #1 of the
MAXI-AMP to establish a voltage reference between the dc supply for the external device and the internal dc supply of the
MAXI-AMP.

ON DELAY:

The ON DELAY timer keeps the output "off" until the selected LIGHT or DARK signal has been present

for the preset "DELAY" time. If the input signal is interrupted, the timing is reset and starts over with the next signal. Grounding
pin #9 immediately cancels an output in progress and resets the delay timer. The delay timer is restarted when the inhibit signal
is removed, if an input signal is present.

OFF DELAY:

The output energizes immediately when the input signal occurs, but does not de-energize until the signal

has been removed for the preset OFF-DELAY ("HOLD") time. Grounding pin #9 prevents an output from occuring. If an
inhibit input occurs during an output, the output remains "on" for the remainder of the OFF-DELAY time.

ON & OFF DELAY:

ON and OFF DELAY logic combines both timing functions into a single mode. The ON-

DELAY ("DELAY") time and the OFF-DELAY ("HOLD") time are independently adjustable within the selected time range.
Momentary grounding of pin #9 during the ON-DELAY period resets the DELAY timer. An inhibit signal which occurs during
an output will allow the output to stay energized for the remainder of the OFF-DELAY time. ON and OFF DELAY logic is
often used in jam and void control, high/low level control, and edge-guiding applications.

ONE-SHOT:

The output of a ONE-SHOT function is a pulse of adjustable "HOLD" duration which is independent

of the duration of the input signal. With the MAXI-AMP programmed for LIGHT operate, the pulse occurs when the input
signal changes from dark to light. In DARK operate, the pulse occurs with a light to dark input transition. Grounding pin #9
prevents the one-shot from triggering, but does not affect a pulse already under way.

DELAYED ONE-SHOT:

A DELAYED ONE-SHOT is initiated by either a momentary or maintained input

signal. This input starts the adjustable "DELAY" period, after which the output pulses for an adjustable pulse ("HOLD") time.
No further action occurs unless the input is removed and reapplied, beginning a new sequence. Grounding pin #9 during the
delay period will cancel the sequence, and no output occurs. This feature is often used for inspection/rejection control logic.
An inhibit signal will not affect a pulse under way.

REPEAT CYCLE:

The REPEAT CYCLE function provides an oscillating output when an input signal is present.

Presence of an input signal triggers an adjustable "DELAY" timer. After the delay, the output energizes for an adjustable
"HOLD" period. If the input remains, the output continues to cycle "on" and "off" at this rate indefinitely. When the signal
is removed, any output in progress completes and then remains "off" until the next signal and DELAY period. Grounding pin
#9 cancels the sequence, but will allow the completion of a "HOLD" period in progress. Lifting the inhibit signal begins the
DELAY period, if an input signal is present.

AC LATCH:

An AC LATCH is the combination of a ONE-SHOT and a LATCH. A momentary or sustained input

will latch the output "on". Grounding pin #9 will reset the latch, even if the input signal remains. The output will not re-latch
until the input signal is removed and then reapplied.

DC LATCH:

The output will latch "on" whenever the selected LIGHT or DARK input condition occurs. Grounding

pin #9 of a dc latch will turn the output "off" regardless of the state of the input signal. If the signal is present when the reset
is removed, the output will immediately latch "on" again.

DELAY AND LATCH:

The DELAY + LATCH is a combination of the ON-DELAY and DC LATCH functions.

An input must be present for at least the adjustable "DELAY" time for the output to latch "on". If the input signal is removed
during the timing cycle, the timing is reset. Momentary grounding of pin #9 resets the latch and/or the DELAY timing cycle.
Sustained grounding of pin #9 inhibits any output.

LIMIT AND LATCH:

The LIMIT + LATCH operates exactly like the LIMIT function, except that the LIMIT

("HOLD") timer can be reset only by the auxiliary input. An output remains latched "off" until reset by momentarily grounding
pin #9. In addition to resetting the timer, grounding pin #9 will hold the output "off", regardless of the state of the input signal.

Description of Logic Functions for CD5, CL5, CM5, and CR5 models

6