Single-point window set – Banner D10 Expert with Numeric Display—Discrete User Manual
Page 8

Single-Point Window SET
Sensor positions
window thresholds
± 100 counts from the
presented condition
Darkest
(no signal)
Most Light
(saturated
signal)
Taught
Condition
200 counts
Hysteresis
100 counts
Hysteresis
100 counts
Output OFF
Output OFF
Output ON
Sensing window size adjusted by
Manual Adjust
Figure 8. Single-Point Window SET and Hysteresis
(Light Operate shown)
• Sets a single ON condition that extends 200 counts above and below
the taught condition (including ±100 counts hysteresis)
• All other conditions (lighter or darker) result in OFF output
• Sensing window size (sensitivity) is adjustable using “+” and “-” buttons
(see
on page 11)
Window SET is most useful when a product may not always appear in the
same place, or when other signals may appear. Window SET designates a
sensing window, with the Output ON condition inside the window, and the
Output OFF conditions outside the window (see
Window SET and Hysteresis (Light Operate shown)
on page 8). The sen-
sor accepts a single sensing condition, and adds switching thresholds and
hysteresis above and below that condition to create a sensing window.
Output ON and OFF conditions can be reversed by changing Light/Dark
Operate status in SETUP mode.
Window SET and Manual Adjust
Discrete: Using Manual Adjust with Window SET expands or contracts the
size of the window.
Analog: Analog manual adjust increases (+) or decreases (-) counts on
both ends by the same amount, but it does not rescale. Cycling the power
will rescale the window and adjustments.
Push Button
Remote
0.04 seconds < T < 0.8 seconds
Result
Access SET
Mode
Press and hold Static (-)
button > 2 seconds.
• Display flashes “1St”
• Arrow icon turns red
• Present sensing condi-
tion
• Single-pulse the remote
line
T
• Display flashes “2nd”
• Arrow icon turns red
SET Sens-
ing Condi-
tion
• Present sensing con-
dition
• Double-click Static
button
Double-pulse the remote
line.
T
T
T
TEACH conditions accep-
ted
• Display flashes “Sn6l,”
then "Pt" twice
• Sensor returns to RUN
mode with new settings
• Arrow icon turns green
TEACH conditions unac-
ceptable
• Display flashes “FAIL”
and returns to “1St”
• Arrow icon remains red
D10 Expert™ - Analog and Discrete Outputs
8
www.bannerengineering.com - tel: 763-544-3164
P/N 65448_web
rev. F