Crown Boiler 24-07 User Manual

Page 12

Advertising
background image

12

G

N

I

N

R

A

W

f

o

n

g

i

s

e

d

e

h

t

n

o

t

r

e

p

x

e

g

n

it

n

e

v

a

tl

u

s

n

o

C

.

y

l

n

o

s

n

o

it

a

d

n

e

m

m

o

c

e

r

e

r

a

s

n

o

it

c

u

r

t

s

n

I

g

n

it

n

e

V

l

a

n

o

it

a

N

e

h

T

d

n

a

e

d

i

u

G

g

n

it

n

e

V

E

A

R

H

S

A

e

h

T

.

n

o

it

a

c

il

p

p

a

r

u

o

y

r

o

f

m

e

t

s

y

s

t

n

e

v

c

if

i

c

e

p

s

a

.

s

m

e

t

s

y

s

g

n

it

n

e

v

ll

a

n

i

d

e

r

e

d

i

s

n

o

c

e

b

d

l

u

o

h

s

4

5

A

P

F

N

,

e

d

o

C

s

a

G

l

e

u

F

k

a

e

l

n

a

c

s

e

s

a

g

e

u

l

F

.

n

o

it

a

c

il

p

p

a

e

h

t

r

o

f

e

l

b

a

ti

u

s

e

b

t

o

n

y

a

m

l

a

i

r

e

t

a

m

t

n

e

v

l

a

n

o

it

n

e

v

n

o

C

y

r

u

j

n

i

l

a

n

o

s

r

e

p

e

r

e

v

e

s

n

i

tl

u

s

e

r

n

a

c

d

n

a

s

l

a

i

r

e

t

a

m

e

s

e

h

t

n

o

s

t

n

i

o

j

e

h

t

m

o

r

f

e

d

i

x

o

n

o

m

n

o

b

r

a

c

.

h

t

a

e

d

r

o

ll

i

w

s

w

o

b

l

e

r

o

s

e

e

t

f

o

t

n

u

o

m

a

e

v

i

s

s

e

c

x

e

n

a

r

o

s

n

u

r

l

a

t

n

o

z

i

r

o

h

g

n

o

l

g

n

i

v

a

h

s

n

o

it

a

ll

a

t

s

n

I

f

o

e

g

a

k

a

e

l

s

a

g

e

u

lf

,

n

o

it

a

s

n

e

d

n

o

c

n

i

tl

u

s

e

r

n

a

c

d

n

a

s

e

s

a

g

n

o

it

s

u

b

m

o

c

f

o

w

o

lf

e

h

t

t

c

i

r

t

s

e

r

.

h

t

a

e

d

r

o

y

r

u

j

n

i

l

a

n

o

s

r

e

p

e

r

e

v

e

s

n

i

g

n

it

l

u

s

e

r

,

e

d

i

x

o

n

o

m

n

o

b

r

a

c

If the venting system is designed for positive or forced

draft venting, the boiler, vent connector and stack will

operate under positive pressure. Gas tight vent systems

designed for pressure systems must be used to prevent

flue by-product leakage. The vent height is usually

limited to prevent negative draft, typically three (3)

feet above the roof line (see Figure 3a). The damper

shall be adjusted to maintain a positive pressure of 0.1”

W.C. in the vent connector box during burner high fire

operation (see breeching pressure sensing port in Figure

1).

If the venting system is designed for negative pressure

(natural draft), the boiler still operates with positive

pressure in the chamber and up to the fixed damper on

the flue collar. However, if the venting system is larger

than what is required, the stack will provide a surplus

draft (or negative pressure) that may require the use of

a barometric damper to maintain the positive 0.1” W.C.

pressure at the flue outlet. Multiple forced draft boiler

stacks should always be designed as negative to ensure

the products of combustion do not exit a boiler that is

not firing.

FIGURE 3b: VENTS — FAULTS & SUGGESTIONS

TYPICAL VENTS THAT ARE USED ON FORCED DRAFT BOILERS, ON LOW SILHOUETTE BUILDINGS

VENT SIZING - Area must be the same as or greater than the boiler breeching (Smoke Outlet). A barometric damper may be required on

installations with a high draft condition.

FAULTY BOILER BURNER OPERATION

1. If improper vent is suspected, remove pipe at breeching and operate boiler. This will determine if excessive down draft,

blocked or restricted flue, etc. is causing the problem.

2. If using type shown in A above, be sure cap is raised sufficiently above main pipe to allow flue gases to vent unimpeded.

3. A popular type cap is shown in B.

4. The tee is frequently used as shown in C.

5. D and E should not be used due to possible fluctuations in back pressure.

B

RAIN CAP

RIGHT

“A” CAP

RIGHT

TEE TYPE

RIGHT

D

E

WRONG

WRONG

90°

ELBOW

UP or DOWN

A

C

Advertising
This manual is related to the following products: