Warning – Crown Boiler 24-07 User Manual

Page 33

Advertising
background image

33

WARNING

Return water cannot be lower than 135°F for prolonged periods of time. Operation under these

conditions will result in sustained condensing within the combustion chamber and potentially

reduce boiler longevity.

In addition, the return water cannot be introduced into the boiler if it is more than 40°F less than

the idle boiler temperature. Continued operation under these conditions may result in

premature boiler failure through thermal shock.

Example: A boiler that has been idle for some time since the last heat demand cycle may have

it's boiler water temperature reduced to 150°F. The return temperature from the next zone

activation cannot be less than 110°F.

If the above conditions exist, an RTC system must be installed to protect the boiler from

sustained condensing operation and thermal shock.

WARNING

A hot water boiler installed above radiation

level must be provided with a low water

cutoff device as part of the installation.

1. HOT WATER HEATING - This boiler must be

installed in strict accordance to the instructions

found in this installation manual. Deviations

from these installation instructions may void

manufacturer’s warranty. See warning below

to determine the use of the RTC. A Return

Temperature Control (RTC) may be provided to

protect the boiler from thermal shock and sustained

condensing operation. In addition, a properly

selected boiler circulator and diverting valve, along

with the return sensor, must be installed when using

the RTC. A number of typical Crown applications

have been added to the appendix (Appendix A).

Select the appropriate application before proceeding.
a. Parallel Piping Systems – An existing parallel

piping system may be used, provided the return

water is not below 135°F for prolonged periods

of time, and the return water temperature is

not more than 40°F less than the idle boiler

temperature (see warning below). A flow

analysis should be performed to determine the

flow through the boiler when the minimum (and

smallest) and maximum number of zones are

activated. A sufficient flow through the boiler

should be maintained to assure a maximum of

40°F difference between the boiler supply and

return.

If the conditions above cannot be met, then

parallel piping systems must be converted to a

primary/secondary arrangement, de-coupling

the system pump from the boiler loop. The

system pump cannot influence the flow through

the boiler(s) in a primary/secondary piping

arrangement. The concept must be for the boiler

loop to inject heat into a primary loop, provided

the return water into the boiler is at least 135°F.

A by-pass containing two closely spaced tees

must be installed to de-couple the boiler loop

from the primary loop (see Figure 30). Care

must be taken to avoid dead heading the

system pump. Conversions should be reviewed

and approved by a Consulting Engineer or

other qualified professional to avoid system

deficiencies.

b. Primary/Secondary Piping – Boiler(s) must

be installed into a heating system that is

(are) designed as a primary/secondary piping

arrangement when the flow through the boiler

cannot be maintained to provide a 20°F - 40°F

difference between the boiler supply and

return. When using an RTC, the boiler loop

contains a boiler, boiler circulator and diverting

valve, along with the return temperature control

(RTC) and return sensor. The diverting valve

consists of a 3-way valve, positioned through

the use of an electronic actuator. The boiler loop

injects heat into the primary loop, provided the

temperature of the boiler return water is greater

than 135°F. If the temperature is below 135°F,

the diverting valve closes, recirculating the

boiler water until it has heated above the 135°F

minimum limit. The supply and return of the

boiler loop is connected to the primary loop

through the use of two closely spaced “Tees”, at

a maximum branch centerline distance of 4 times

the primary loop diameter (4 x D Max.) The

RTC provides a signal to the actuator based on

the absolute water temperature and the rate of

change in water temperature.

c. Multiple Boilers – Multiple boilers are installed

the same as single boiler installations. Each

boiler loop will contain it’s own boiler circulator,

diverting valve, RTC and return sensor (see

Appendix A). Commonly available sequencers

can be used in conjunction with the Return

Temperature Control by energizing the control’s

heat demand circuit. The outdoor reset feature

of the sequencer must be used in multiple

boiler installations. The outdoor reset feature

Advertising
This manual is related to the following products: