CONNECT TANKLESS HEATER PIPING as

shown in Figure 38. See Table IV for Tankless Heater

Ratings.

1. Install Flow Regulator
If flow through the heater is greater than its rating,

the supply of adequate hot water may not be able to

keep up with the demand. For this reason a FLOW

REGULATOR matching the heater rating should be

installed in the cold water line to the heater. Refer

to Figure 36 for piping recommendations. Locate

the flow regulator below the inlet (cold water side)

of the heater and a minimum of 36” away from the

inlet so that the regulator is not subjected to excess

temperatures during “off” periods when it is possible

for heat to be conducted back through the supply

line. The flow regulator will limit the flow of supply

water regardless of inlet pressure variations ranging

from 20 to 125 psi.

2. Install Water Temperature Mixing Valve

Refer to Figure 38 for piping recommendations.

Adjust and maintain the mixing valve in accordance

with manufacturer’s instructions.

Installation of a mixing valve will also lengthen the

delivery of the available hot water by mixing some

cold water with the hot. In addition, savings of hot

water will be achieved since the user will not waste

as much hot water while seeking desired water

temperature. Higher temperature hot water required

by dishwashers and automatic washers is possible

by piping the hot water from the heater prior to

entering the mixing valve. An electric hot water

booster can also be used. The mixing valve should

be “trapped” by installing it below the cold water

inlet to heater to prevent lime formation in the valve.

3. Flushing of Heater

All water contains some sediment which settles

on the inside of the coil. Consequently, the heater

should be periodically backwashed. This is

accomplished by installing hose bibs as illustrated

in Figure 38 and allowing water at city pressure to

run into hose bib A, through the heater, and out hose

bib B until the discharge is clear. The tees in which

the hose bibs are located should be the same size as

heater connections to minimize pressure drop.

4. Hard Water
A water analysis is necessary to determine the

hardness of your potable water. This is applicable

to some city water and particularly to well water.

An appropriate water softener should be installed

based on the analysis and dealer’s recommendation.

This is not only beneficial to the tankless heater but

to piping and fixtures plus the many other benefits

derived from soft water.

NOTICE

The following guidelines should be followed

when piping the tankless heater:

WARNING

Install a mixing valve at the tankless heater

outlet to avoid risk of burns or scalding

due to excessively hot water at fixtures.

Do not operate the boiler when equipped

with a tankless heater unless mixing valve

is operating properly.

CAUTION

Do not operate tankless heater with hard

water. Tankless failure will result. Install

water softener if hard water is present.

Figure 36:

Mounting Elevations

of M&M 150, 64 and 67

Float Low Water Cut-offs.

"A"

"B"

67

35-1/2"

-

64

-

37-1/2"

150

-

40"

Primary or Secondary

Primary (Gravity Return)

Primary (Pumped Return)

Cut-Off Height

Application

L.W.C.O.

“A”