Crown Boiler 24-07 User Manual

Page 43

Advertising
background image

43

Figure 40a: Steam Boiler - Safety Valve Hook-Up

Figure 39b: Diverting Valve/Actuator Wiring

(CW - Open to System)

Figure 39a: Diverting Valve/Actuator Wiring

(CCW - Open to System)

N.

ELECTRIC WIRING - Install all field wiring in

accordance with the National Electric Code and Local

Regulations.

Control voltage and/or 3-phase line voltage must

be supplied to the burner panel box through a fused

disconnect.

When using the RTC, a separate fused control circuit

shall feed the control to allow the exercising of the

valve actuator and boiler circulator during dormant

boiler operation.

Review electrical schematics in Appendix A and Burner

Electrical Diagram for more information.

O.

RETURN TEMPERATURE CONTROL AND

COMPONENTS
1. Valve Actuator – The valve actuator is mounted to

the top of the diverting valve. Mount and connect

the actuator as illustrated in Appendix C. The

electrical connections depend on valve orientation.

Use Figures 39a and 39b as a guide.

2. Return Sensor – A sensor has been included with

the Return Temperature Control. The sensor must

be mounted for proper operation. The sensor is

mounted in the 3 inch NPT x 12 inch special return

nipple. The sensor must be inserted into the ¼ NPT

connection using pipe dope. The 3” nipple must be

inserted with the sensor closest to the boiler, using

the rear lower right connection. (Orientation based

on viewing the boiler from the rear.) The sensor

shall be connected to the RTC through a junction

box located above the nipple. Use grommets and

conduit to protect the leads and connection back to

the RTC controller.

3. Knock Down Boiler Installations – The installation

instructions above must be followed for all

knockdown boilers as well. The controller is

mounted on the front jacket panel at the top right.

See Figures 41 and 42 for general component

Advertising
This manual is related to the following products: