ASHRAE Fundamentals for the area closest to

the installation. This value has a default of 10°F,

and is adjustable between –60ºF to 32ºF.

e. WWSD – The Warm Weather Shut Down feature

is used only when the outdoor reset feature

is selected. (OUTDR DESIGN = ON) If the

outdoor temperature rises above the WWSD

value, WWSD will be displayed. If a demand

for heat is generated when the control is in the

WWSD mode, the boiler will be disabled. The

default for the WWSD is 70ºF, but is adjustable

from 35ºF to 100ºF.

f. MIX MIN – This represents the minimum mix

target supply temperature when the outdoor reset

feature is selected. (OUTDR DESIGN = ON)

This is the lowest temperature the controller is

allowed to use as a MIX TARGET temperature.

During mild conditions, if the RTC calculates a

MIX TARGET below the MIX MIN, the target

will be adjusted to match the MIX MIN setting.

g. MIX MAX – This represents the highest

temperature allowed as the MIX TARGET

temperature when the outdoor reset feature is

selected. (OUTDR DESIGN = ON) If the RTC

calculates a MIX TARGET higher than the MIX

MAX, the MIX TARGET will take the value of

the MIX MAX. Typically, this is set between

200ºF and 220ºF. The temperature must be set

below the lowest permissible temperature for

any system related component affected by boiler

supply water.

h. OPEN DELAY – This value represents the

number of seconds required for the actuator to

open through 90 degrees of rotation. Leave in

default value of 50 seconds.

i. BOIL MIN – This is the minimum boiler return

temperature allowed. The minimum value has

been set to 135ºF, adjustable to as high as 230ºF.

The RTC will control the diverting valve while

maintaining a minimum BOIL MIN temperature.

Setting should remain at 135ºF unless a higher

minimum boiler temperature is required.

j. BOIL MIN DELAY – This represents the time

(in seconds) required for warm-up during an

initial cold start. This prevents the counter

from including cold start warm up time in the

total boiler operation time below 135ºF. This

grace period is provided for every heat demand

cycle until 135ºF has been sensed at the return

sensor. Once the return sensor has sensed a

return temperature reading of 135ºF, after the

heat demand cycle has initiated, the grace period

is terminated. The warm up time includes a 90

seconds of pre-purge time. Use the values in

Table V for the correct application.

k. PUMP DELAY – Pump delay represents the

time (in seconds) for pump purge (boiler

r

e

li

o

B

l

e

d

o

M

Y

A

L

E

D

N

I

M

L

I

O

B

)

s

d

n

o

c

e

S

(

3

0

-

4

2

0

4

5

4

0

-

4

2

0

6

4

5

0

-

4

2

0

1

4

6

0

-

4

2

0

7

3

7

0

-

4

2

0

6

3

8

0

-

4

2

0

4

3

9

0

-

4

2

0

2

3

0

1

-

4

2

0

1

3

1

1

-

4

2

0

0

3

2

1

-

4

2

0

9

2

circulator purge) after a heat demand cycle. This

minimizes the amount of boiler temperature

overshoot at the end of a boiler cycle. During

the pump purge the diverting valve will

continue to operate and prevent low return water

temperatures from entering the boiler. At the

end of the pump purge period the diverting valve

will be immediately closed. The default PUMP

DELAY is set to 30 seconds.

l. UNITS – The temperature units can be changed

to either Fahrenheit or Celsius. The default

temperature unit is Fahrenheit.

4. ERROR MESSAGES – Error messages are shown

on the LED display. The function in error will be

shown as a black background label in the LED.

Most of the errors indicate an open or short circuit,

connected to the RTC. The RTC Installation and

Maintenance Manual identifies common errors.

Cycle through the error messages and repair as

required.
a. Return Sensor Error – If the return water

temperature sensor has been damaged or omitted,

the BOIL item will be displayed as either a

“short” or “open” circuit. This will force the

mixing device (i.e. 3-way valve) to run at a

fixed 30% open position. The system may not

receive enough heat nor will it be fully protected,

however a significant change will be obvious to

occupants and/or operators.

b. Operation Below Minimum – If the return sensor

has been damaged or omitted, and the return

water is allowed to return to the boiler below

135ºF, the BOIL MIN field will be displayed

along with ERR. The failure must be identified

and repaired immediately since the boiler

has been operating in a condition that fosters

premature boiler failure.