Warning – Crown Boiler 24-07 User Manual

Page 32

Advertising
background image

32

WARNING

Failure to properly pipe boiler may result in

improper, unsafe system operation and void

manufacturer's warranty.

DO NOT improperly pipe boiler.

WARNING

All steam and hot water pipes must have

clearances of at least 1/2" from all

combustible construction.

I.

WATER BOILERS - INSTALL WATER TRIM

Items for water trim are located in the water trim carton

(except for the separately ordered low water cutoff and

tankless heater control). Figures 26a and 26b show the

proper tappings for each item.
1. Install the temperature pressure gauge.
2. Install the low water cutoff (supplied by others).

Follow manufacturer’s instructions furnished with

control.

3. Install the immersion well and mount the aquastat

(limit control) onto the well.

4. Install the pressure relief valve as shown in Figure

40b. Relief valve must be installed in vertical

position.

5. Plug extra boiler tappings.
6. Install required bottom blowoff/drain valve

(supplied by others) per minimum piping

requirements for water boilers, see Figures 31, 32

and 33.

WARNING

Relief valve discharge piping must be piped

within six (6) inches of floor or to floor

drain to eliminate potential of severe burns.

Do not pipe in any area where freezing

could occur. Do not install any shut-off

valves, plugs or caps in discharge piping.

J.

BURNER INSTALLATION

Refer to burner manufacturer’s installation manual

for proper installation, fuel piping, wiring, burner

adjustment, burner start-up and service instructions.

Consult Section VI of this manual for burner

specifications and burner settings.

K.

BOILER PIPING - HEATING APPLICATIONS

CONNECT SUPPLY AND RETURN PIPING TO

HEATING SYSTEM (see Figures 31, 32 and/or 33 for

water boilers and Figures 34 and 35 for steam boilers).