of installation.

5. ON WATER BOILERS WITH TANKLESS

HEATERS, set low limit operating control dial at

190°F and high limit dial 210°F. Operating control

must be a minimum of 20° below high limit setting.

Set differential at 25°.

D.

ADJUST BURNER according to the Burner Manual.

1. FLAME FAILURE
The Series 24 boiler controls operate the burner

automatically. If for unknown reasons the burner

ceases to fire and the reset button on the primary

control is tripped, the burner has experienced

ignition failure. Before pressing the reset button,

call your serviceman immediately.

WARNING

Do not attempt to start the burner when

excess oil or gas has accumulated in the

combustion chamber, when the unit is full

of vapor, or when the combustion chamber

is very hot.

E.

RETURN TEMPERATURE CONTROL: Initial

Set-Up and Operation – The return temperature

control (RTC) is an important part of the overall boiler

system. The primary function of the RTC is to protect

the boiler from thermal shock and sustained flue gas

condensation. The RTC monitors the temperature of

the water returning into the boiler through a return

sensor. The RTC controls the 3-way diverting valve

mounted on the supply of the boiler to prevent return

water less than 135º F from entering the boiler. The

boiler circulator provides constant and minimum flow

through the boiler during every heat demand. Prior

to the start of any boiler cycle, the diverting valve is

closed to a full by-pass condition, forcing 100% boiler

water re-circulation. The diverting valve opens and

will continue to open provided the return sensor is

satisfied. Conversely, large temperature drops will

close the diverting valve to a position as to prevent

low temperature return water. The RTC along with

the ancillary components must be properly installed

as identified in Section III, if there is any possibility

of system return water temperature less than 135°F. A

detailed description of the controller and it’s features

can be found in the RTC Installation and Maintenance

Manual.
1. Initial Start-up - Upon initial start-up, the control

will be energized, identifying the control name and

revision on the LED display. If wired properly, the

control should be energized at all times. The RTC

circuit should be supplied from a different source

than the burner or boiler circuit. The RTC control

should be energized at all times.

2. Testing – The RTC should be tested on initial start-

up, as well as during any troubleshooting exercise.

Depressing the test button will activate a test

sequence and energize the red test light on the front

of the control. Each of the controllers outputs and

relays will be energized and tested. One may pause

the test sequence at any time by depressing the test

button. See the RTC Installation & Maintenance

Manual for a detailed description of the sequence

and the potential error messages.
a. Return Sensor - The return sensor must be

properly connected or an error message will be

displayed. Both a short and an open circuit in

the sensor circuit will cause an error message to

be displayed and the valve will be moved to a

partially open position until the error is resolved.

b. Valve Actuator – During the valve actuator test

sequence, confirm that the valve travels through

90 degrees of rotation from a full closed position

to a full open position. The pointer on the shaft

must rotate from “10” to “0” respectively.

3. Adjust Setpoints – The RTC must have a number of

setpoints adjusted for proper operation. Below is

a summary, however see the RTC Installation and

Maintenance Manual for more details. To activate

the ADJUST menu, simultaneously depress and

hold the Item,  and  buttons. ADJUST will

appear in the upper right hand corner of the LED

display.
a. ROOM - Set desired room temperature. This

will provide parallel shift to heating curve.

OUTDR DESIGN OFF

b. MIX TARGET – This represents a fixed target

supply temperature when the outdoor reset

feature in NOT selected. (OUTDR DESIGN =

OFF) Set the MIX TARGET temperature to the

designed boiler supply temperature. Example:

If the boiler loop is designed to supply hot water

to the system at 180ºF, set the MIX TARGET

to 180ºF. This is also the same as the operating

aquastat set point. The mix target is adjustable

from 60°F to 200ºF. The default setting is 180°F.

NOTE: This function is only for applications

where the mix sensor is installed.

c. MIX DSGN – Mix design temperature represents

the design heating system supply temperature

when the outdoor reset feature is selected.

(OUTDR DESIGN = ON) This represents the

design of the system loop. If unsure of the

original design temperature, set the MIX DSGN

to the same temperature as the boiler operating

aquastat, typically 180ºF. The MIX DSGN is

adjustable from 70°F to 210ºF. The default

setting is 180°F.

d. OUTDR DSGN – The outdoor design

temperature represents the value used in the

heat loss calculations, when the outdoor reset

feature is selected. (OUTDR DESIGN = ON) If

this value is unknown, use the value found in

Advertising