Warning – Crown Boiler 24-07 User Manual

Page 50

Advertising
background image

50

J.

TEST CONTROLS

WARNING

Before installation of the boiler is

considered complete, the operation of the

boiler controls should be checked,

particularly the low water cutoff and the

high limit control.

All controls must be checked prior to putting the boiler

in service.

1. CHECK OPERATING CONTROL OPERATION.

Raise and lower operating control setting as required

to start and stop burner.

2. CHECK OPERATION OF HIGH LIMIT

CONTROL —

Jumper Operating Control Terminals. Allow burner

to operate until shutdown by limit. Installation is

not considered complete until this check has been

made. REMOVE JUMPER.

3. CHECK LOW WATER CUTOFF control with water

level at normal water line (see Figure 1). Raise

operating control setting to allow burner to operate.

Open boiler drain to allow water level to drop to

bottom of sight glass until burner operation is shut

down by low water cutoff.

Close boiler drain and refill to normal water line.

Burner should automatically restart during fill.

RESET OPERATING CONTROL.

both the boiler circulator and the diverting valve

during periods of dormant activity provided power

is supplied to the control.

F.

DIVERTING VALVE ACTUATOR - A 3-way

diverting valve is used to control the temperature of

the water returning to the boiler. Proper operation

is required to protect the boiler from thermal shock

and sustained condensate production. Confirm the

operation of the valve as shown above. See Figures 39a

and 39b.

G.

BOILER OPERATING AQUASTAT – The operating

aquastat, L4006A, can be found on the front of the

boiler, to the right of the temperature/pressure gauge.

The operating aquastat should be set to the designed

supply temperature, typically 180ºF. The operating

aquastat set point, the RTC MIX TARGET or the RTC

MIX DESGN, should be set to the same value for

20°F ∆T applications. In 40°F ∆T applications, the

operating aquastat (L4006A) must be set 20°F higher

than the MIX TARGET and MIX DESIGN . Under

no circumstances should the operating aquastat be set

below 135ºF plus (+) the designed boiler temperature

drop, ∆T (ºF).
Example: if the flow rate through the boiler

corresponds to a 20ºF ∆T design, the operating

aquastat cannot be set lower than 135 + 20 = 155ºF.

In reality, most systems are designed for a 180ºF supply

water and 160ºF return water. The accuracy of the

operating aquastat is less than the RTC accuracy, often

requiring the operating aquastat temperature to be

bumped upward a few degrees.

H.

BOILER HIGH LIMIT AQUASTAT – If used, the

high limit aquastat, L4006E, can be found on the front

of the boiler, to the left of the temperature/pressure

gauge. The high limit aquastat can be identified with a

red manual reset button. Ideally, the high limit aquastat

should be set 10 -15°F above the RTC MIX MAX

setting, when the outdoor reset feature is selected.

Typically, this is set between 200ºF and 220ºF. The

temperature must be set below the lowest permissible

temperature for any system related component affected

by boiler supply water. Under no circumstances can the

high limit aquastat be set higher than 250ºF.

I.

BOILER MODULATING CONTROL – Various

controls are used to modulate burner firing rates.

No attempt will be made to cover every possibility,

however a general outline will be given.

Most modulation controls require the entry of a

boiler temperature identifying boiler operation at the

maximum firing rate. A boiler operating temperature

below that will also generate a full firing rate. When a

boiler heat demand is generated the unit will initiate at

either a low or high fire rate and quickly ramp up to the

high fire rate. The unit will continue to fire at the high

fire rate until the boiler high fire modulating limit is

reached.

Many modulation controls require the entry of a burner

off or low fire setting. The burner will modulate

between the high fire and low fire rate based on the

absolute boiler temperature as well as the rate of change

in boiler temperature.

If using a T991 Proportional Control or a similar

modulating device in a traditional hydronic system,

the minimum setting shall be the sum of the designed

heating system return temperature + boiler ∆T + 10°F.
Example: System Supply 180°F
System Return 160°F
System ∆T

20°F

Boiler ∆T

40°F

Min. Setting = 160°F + 40°F + 10°F
= 210°F
*NOTE: A higher flow through the boiler, achieving

a 20°F ∆T would lower the minimum to 190°F.

If using the same control in a system where the

designed return is less than 135°F, then the minimum

becomes:

135°F + Boiler ∆T + 10°F

Advertising
This manual is related to the following products: