Caution, Warning, Danger – Crown Boiler 24-07 User Manual

Page 47

Advertising
background image

47

SECTION IV - OPERATING INSTRUCTIONS

A.

ALWAYS INSPECT INSTALLATION BEFORE

STARTING BURNER.

B.

FILL HEATING SYSTEM WITH WATER.

Boiler must be cleaned and fully free of oil and dirt.

CLEAN HEATING SYSTEM IF boiler water or

condensate return water is dirty or if erratic water lines

or surging exist after a few days of boiler operation.

Refer to step (K) for proper cleaning instructions for

steam and water boilers.
1. STEAM BOILERS - Fill boiler to normal water

line. As shown in Figure 1, the normal water line

is 41½” from the floor or bottom of casting. At

the start of each heating season and once or twice

during the season try SAFETY VALVE to be sure it

is in working condition. To do this, fasten wire or

cord to lever of valve and pull lever — standing safe

distance away from valve.

2. HOT WATER BOILERS - Fill entire Heating

System with water and vent air from system. Use

the following procedure on a Series Loop or Multi-

zoned System to remove air from system when

filling:

a. Close isolation valve in boiler supply piping.
b. Isolate all circuits by closing zone valves or

balancing valves.

c. Attach a hose to bib cock located just below

isolation valve in boiler supply piping.

(Note - Terminate hose in five gallon bucket at a

suitable floor drain or outdoor area).

d. Starting with one circuit, open zone valve.
e. Open bib cock.
f. Open fill valve (Make-up water line should be

located directly above isolation valve in boiler

supply piping).

g. Allow water to overflow from bucket until

discharge from hose is bubble free for 30

seconds.

h. Open zone valve to the second zone to be

purged, then close the first. Repeat this step until

all zones have been purged, but always have one

zone open. At completion, open all zone valves.

i. Close bib cock, continue filling the system until

the pressure gauge registers normal system

design operating pressure. Close fill valve.

(Note - If make-up water line is equipped

with pressure reducing valve, system will

automatically fill to normal system design

operating pressure. Leave globe valve open.)

j. Open isolation valve in boiler supply piping.
k. Remove hose from bib cock.

C.

SET CONTROLS with burner service switch turned

“OFF”.

1. PRESS RESET BUTTON on primary control and

release.

2. On STEAM BOILERS set cut-in pressure on

L404A Pressuretrol for three (3) PSI and differential

pressure for two (2) PSI. These pressures may be

varied to suit individual requirements of installation.

3. On STEAM BOILERS WITH TANKLESS

DOMESTIC WATER HEATERS, set boiler water

temperature dial on low limit operating control at

190°F (max.). Set differential at 10°.

4. ON WATER BOILERS WITHOUT TANKLESS

HEATERS, set high limit dial on L4006A at 210°F.

This temperature may be varied to suit requirements

WARNING

If you do not follow these instructions

exactly, a fire or explosion may result

causing property damage or personal

injury.
If any unusual or improper operation or

site conditions are observed, turn the

boiler off and contact an experienced

and skilled service agency.
Follow component manufacturer’s

instructions. Component manufacturer’s

instructions were provided with the

boiler. Contact component manufacturer

for replacement if instructions are

missing. Do not install, start up, operate,

maintain or service this boiler without

reading and understanding all of the

component instructions. Do not allow

the boiler to operate with altered,

disconnected or jumpered components.

Only use replacement components

identical to those originally supplied with

the boiler and burner.

CAUTION

Failure to clean the system will result in

erratic water lines and surging, and other

improper system operations.

DANGER

Do not operate boiler with pressure

above maximum allowable working

pressure listed on the Boiler Rating

Label.
DO NOT draw water from boiler while in

use. When adding water while boiler is

in operation, do not open supply valve

fully but add water slowly.

Advertising