Electric Latch Retraction Exit Device Wiring

Notes:
1. Power input Door Operator Unit is at Power Input

Terminal Strip (not shown) 120VAC 60Hz.

2. Refer to Manufactures wiring instructions for Latch

Retraction Devices not shown.

3. Power Supply must be .900 Amps minimum per 56-

Latch Retraction Exit Device.

4. Set switch SW2 to position 3 for 1 second delay.

56-

Latch Retraction Exit Device

Operation:

Door is normally closed and latched.

Activating the switch will retract the exit device then the

operator will open the door.

The door will close after the hold open time delay has

elapsed.

Exit device allows egress at all times. Exit device allows

egress during power failure.

5

678

90

1

23

4

5

678

90

1

23

4

5

678

90

1

23

4

5

678

90

1

23

4

JP3

JP2

CL/AS DLY VEST DLY

EXSOL DLY

M. DLY

G

EM

G

H+

V
L

2
G

L1

MO

T

O

R/SOLENOID

JP4

JP1

JP5

OFF

ON

SW1

P/A
A/D

RES1
RES2

0/0

RES1

A

UX2

GND

INV

OUTV

GND

R

F

T

GND

A

UX2

GND

PDET

GND

A

UX1

GND +24V NO1 CO1 NC1 NO2 CO2 NC2

NEU HOT GND

18VAC

1 2 3 4 5 6 7 8

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts

(+)

(-)

120 VAC

24VDC

Filtered and Regulated

Power Supply

*See Note 3

+24VDC

-24VDC

RED

BLACK