Prefix 80 series exit device, Dip switch settings 6 – SARGENT 57 - Delayed Egress User Manual

Page 10

Advertising
background image

S2-5

Reverse LED - Field selectable green or red. When S2-5 is “Off” the exit device LED is green when in armed
mode (default) and

red when in maintained or momentary egress mode. When S2-5 is “On” the exit device

LED is

red when in armed mode and green when in maintained or momentary egress.

5 6

S2-6

OFF

ON

5 6

S2-5

OFF

ON

S2-6 Off - LHRB; Top LED indicates “Armed”
S2-6 On - RHRB; Top LED indicates “Armed”

S2-5 On - Red (Armed); Green (maintained or momentary egress)
S2-5 Off - Green (Armed); Red (maintained or momentary egress)

S2-6 Handing - Field selectable LHRB or RHRB. For a LHRB exit device S2-6 is “Off” for the top LED on the insert
to be used when the device is armed. For a RHRB exit device S2-6 is “On” for the top LED on the insert to be
used when the device is armed.

S2-1

Nuisance Delay - (Field selectable 0 or 1 second) A one second nuisance delay can be enabled by setting Dip
Switch (S2-1) to the “On” position. When nuisance delay is enabled, the unit will require the push bar to be de-
pressed for more than one second in order to trigger an irreversible alarm condition. If the push bar is released be-
fore the 1 second has elapsed, the unit will go back into the “delayed egress mode” and the alarm will not sound.
Nuisance delay is set to “On” position at factory.

If the Dip Switch S2-1 is in the “Off” position, there will be no nuisance delay and alarm horn will sound immedi-
ately when the push bar is depressed.

S2-2

Nuisance Audible - (Field selectable on or off) An audible horn is enabled by setting Dip Switch S2-2 to the “On”

position. The internal horn will sound as soon as the push bar is depressed, signaling that the device is armed. If
the pushbar is held down for more than 1 second, an irreversible alarm condition begins. If Dip Switch S2-2 is in
the “Off” position, the horn will not sound during nuisance delay.

Nuisance audible is set to “On” position at factory to sound horn when rail is depressed during nuisance delay.

5 6

S2-2

OFF

ON

5 6

S2-1

OFF

ON

S2-2 On - Nuisance Audible On
S2-2 Off - Nuisance Audible Off

S2-1 On - (1) second Nuisance Delay
S2-1 Off - No Nuisance Delay

S2-3 & S2-4 Momentary Egress Time -
Used to select the momentary egress time
of 5, 10, 20 or 40 seconds. This switch is
preset at the factory for five seconds.

S2 Dip Switch Position

S2-3
OFF
OFF
ON
ON

S2-4
OFF
ON
OFF
ON

Momentary Egress
Time

5

seconds (Default)

10

seconds

20

seconds

40

seconds

5 6

S2-4

OFF

ON

5 6

S2-3

OFF

ON

57- Dip Switch Settings

6

10 1-800-810-WIRE • www.sargentlock.com • A7743C

Copyright © 2013, Sargen

t Manufacturing Company

, an A

SS

A AB

LO

Y G

roup company

. All right

s reser

ved

.

Reproductions in whole or in par

t without express writ

ten permission of Sargen

t Manufacturing Company is prohibited

.

04/15/13

57- Prefix 80 Series Exit Device