Prefix 80 series exit device, Wiring (continued) 7 – SARGENT 57 - Delayed Egress User Manual

Page 13

Advertising
background image

Harness

I/O Circuit

Connector Board Function

Pin No.

Pin No.

8-2 J1-1

24VDC Power Supply Input (+)

This input may be tied to the normally closed contact of a building’s fire alarm system.
If the fire alarm is activated, this contact will open, voiding the 15 second delay for egress.

8-1 J1-2

Return - Power Supply -return (-).

8-3 J1-4

Remote Reset - This input may be tied to a momentary normally open contact at

a remote location to reset the device when in alarm. Additionally when the device is armed

this input may be used for momentary egress with the time per the Dip switch settings.

8-4 Chassis Ground

Chassis Ground - The chassis ground wire must terminate at earth ground of the

equipment power supply or the main power source.

8-5 J1-5

External Inhibit Input - Used to provide remote override of the delayed egress

when in the armed condition. Most common external inhibits are: card readers, keypad,
key switches, or remote control console. More than one external inhibit device must be
wired in parallel.

8-6 J1-6

Door Position Sensor - An external door status switch can be connected to

the 57- to provide additional security. If the door status switch is utilized, an
irreversible alarm will sound if the door is forced open while the device is armed.
Unit will not arm if door is not shut. Once the irreversible alarm sounds, it will have
to be reset at the door. If the door status switch is not utilized, connect the Blue wire to
-Return (Black wire) of the 5-pin harness.

8-7

-Return Magnet

8-8 +24VDC Output Magnet
External Magnet Connection - This output can supply up to 275mA load to an external
magnet. This output may be connected to a 24VDC relay module if load shall exceed
275mA.

57- Wiring (Continued)

7

13 1-800-810-WIRE • www.sargentlock.com • A7743C

Copyright © 2013, Sargen

t Manufacturing Company

, an A

SS

A AB

LO

Y G

roup company

. All right

s reser

ved

.

Reproductions in whole or in par

t without express writ

ten permission of Sargen

t Manufacturing Company is prohibited

.

04/15/13

57- Prefix 80 Series Exit Device

Advertising