Electroguard, Prefix 80 series exit device, Electroguard troubleshooting (continued) – SARGENT FM8700 Surface Vertical Rod Exit Device User Manual

Page 34: Default factory setting for 59- shown

Advertising
background image

**

FUNCTION

JUMPER

59-STD

J5-2 & J5-3

57-

J5-1 & J5-2

J5

1 2 3

Default factory setting
for 59- shown

6. With Rim, Mortise and Vertical Rod exit devices:
If jumper (J5) is in wrong position, the latchbolt monitor switch is bypassed (if held, will not go into alarm).

To locate (J5) jumper, remove Insert Assembly and Insert Assembly Plate:

Black ( - )

59-80 Series

Blue

DSS *

Electroguard Troubleshooting (Continued)

MINIMUM REQUIREMENTS FOR ARMING RAIL (DELAYED EGRESS MODE)

* To Arm 59- Rail– The

Blue Door Status Switch (DSS) wire must be connected

directly to the Black wire (-Return) or the contacts must be closed as shown.

The White wire (formerly Green) must be connected to the Black wire (-Return)

as shown.

-Return

+24VDC

* Only these (3) wires are needed to arm rail along with the correct

LBM switch and Push Rail Switch position as shown previously

**

Fire Alarm Contact (if required)

Red ( + )

11

NOTES

1. With Rim and Mortise type exit devices - When the latch bolt is retracted about

half-way, the

Yellow Diagnostic LED turns ON. The LED will be ON from half-

way to the fully retracted position; otherwise the LED will be OFF.

2. With Vertical Rod type exit devices – When the rods are retracted and the door is opened, the Rod Monitor

Switch is activated and the

Yellow Diagnostic LED turns ON. The LED will remain on until the door closes

and the rods are reset and engaged.

3. When the rail is armed (in Delayed Egress Mode) and the door is closed and latched, the

Green (default)

or Red LED and the Green Diagnostic LED should be ON only. All other LEDs should be OFF.

4. With the rail armed, depressing the rail push bar slightly will turn the

Red Diagnostic LED ON. The rail

should go into alarm immediately (no nuisance delay) or after being pressed in for 1 second (1-second

nuisance delay). The rail will be in the irreversible alarm mode –

Insert Green and Red LED flash and the

rail horn sounds. After a standard delay of 15 seconds (or 30-second optional delay), the rail magnet de-

energizes and passage is allowed. The rail horn will continue to sound until the rail is reset with a key.

5. When a Door Status switch is used and the door is opened the

Orange Diagnostic LED will turn ON,

which indicates that the door is not secure. When NOT using a Door Status switch, the Blue wire should be

connected to Black (-Return). In this case, the LED will always be OFF.

34 1-800-810-WIRE • www.sargentlock.com • A7690E

Copyright © 2013, Sargen

t Manufacturing Company

, an A

SS

A AB

LO

Y G

roup company

. All right

s reser

ved

.

Reproductions in whole or in par

t without express writ

ten permission of Sargen

t Manufacturing Company is prohibited

.

04/15/13

Electroguard

®

59- Prefix 80 Series Exit Device

Advertising