Electroguard, Prefix 80 series exit device, Electroguard troubleshooting (continued) – SARGENT FM8700 Surface Vertical Rod Exit Device User Manual
Page 34: Default factory setting for 59- shown
**
FUNCTION
JUMPER
59-STD
J5-2 & J5-3
57-
J5-1 & J5-2
J5
1 2 3
Default factory setting
for 59- shown
6. With Rim, Mortise and Vertical Rod exit devices:
If jumper (J5) is in wrong position, the latchbolt monitor switch is bypassed (if held, will not go into alarm).
To locate (J5) jumper, remove Insert Assembly and Insert Assembly Plate:
Black ( - )
59-80 Series
Blue
DSS *
Electroguard Troubleshooting (Continued)
MINIMUM REQUIREMENTS FOR ARMING RAIL (DELAYED EGRESS MODE)
* To Arm 59- Rail– The
Blue Door Status Switch (DSS) wire must be connected
directly to the Black wire (-Return) or the contacts must be closed as shown.
The White wire (formerly Green) must be connected to the Black wire (-Return)
as shown.
-Return
+24VDC
* Only these (3) wires are needed to arm rail along with the correct
LBM switch and Push Rail Switch position as shown previously
**
Fire Alarm Contact (if required)
Red ( + )
11
NOTES
1. With Rim and Mortise type exit devices - When the latch bolt is retracted about
half-way, the
Yellow Diagnostic LED turns ON. The LED will be ON from half-
way to the fully retracted position; otherwise the LED will be OFF.
2. With Vertical Rod type exit devices – When the rods are retracted and the door is opened, the Rod Monitor
Switch is activated and the
Yellow Diagnostic LED turns ON. The LED will remain on until the door closes
and the rods are reset and engaged.
3. When the rail is armed (in Delayed Egress Mode) and the door is closed and latched, the
Green (default)
or Red LED and the Green Diagnostic LED should be ON only. All other LEDs should be OFF.
4. With the rail armed, depressing the rail push bar slightly will turn the
Red Diagnostic LED ON. The rail
should go into alarm immediately (no nuisance delay) or after being pressed in for 1 second (1-second
nuisance delay). The rail will be in the irreversible alarm mode –
Insert Green and Red LED flash and the
rail horn sounds. After a standard delay of 15 seconds (or 30-second optional delay), the rail magnet de-
energizes and passage is allowed. The rail horn will continue to sound until the rail is reset with a key.
5. When a Door Status switch is used and the door is opened the
Orange Diagnostic LED will turn ON,
which indicates that the door is not secure. When NOT using a Door Status switch, the Blue wire should be
connected to Black (-Return). In this case, the LED will always be OFF.
34 1-800-810-WIRE • www.sargentlock.com • A7690E
Copyright © 2013, Sargen
t Manufacturing Company
, an A
SS
A AB
LO
Y G
roup company
. All right
s reser
ved
.
Reproductions in whole or in par
t without express writ
ten permission of Sargen
t Manufacturing Company is prohibited
.
04/15/13
Electroguard
®
59- Prefix 80 Series Exit Device