56- Electric Latch Retraction Exit Devices

Installation and Wiring Instructions

With Optional 53- Latchbolt; 55- Request to Exit;

and TL- (SARGuide) Connection Instructions

FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com

SIgNaL

CauSE

TRoubLEShooTINg

Dark / Unlit

Controller microprocessor is not active

Confirm connections and incoming power

Steady Flashing

Normal operation

Cycle device by closing the timer circuit

Solid Light

Input voltage is dropping out of operating range

Check wire run and power supply output

2 Flashes Followed by Pause

Sensor or motor issue

Call 800-810-WIRE for assistance

3 Flashes Followed by Pause

Mechanical issue

Call 800-810-WIRE for assistance

6. LED Signalling Chart

4. TIMER MODE Adjustment (Onboard Timer)

How it works: The 24 volt input is always energized and the system retracts when the timer input circuit is closed.

When the timer circuit is closed utilizing a

momentary switch, the device retracts, remains retracted for a set duration,

and releases. The duration of the retraction is set using an onboard timer setting (0 - 20 second timer adjustment).
The countdown begins when the rail is first retracted.

When the timer circuit is closed using a

maintain switch, the device retracts.

The device releases when the circuit is re-opened.

Notes:

Note: 24V supply is constant in

TIMER MODE. The duration of retraction is determined by whichever is longer:

the maintain switch closure or the onboard timer delay.

If more than 20 seconds delay is necessary (exceeding the maximum setting), an external timer delay relay
is required (not provided).

NOTE: Refer to settings in Section III, part 5 (Fig. 19-21) for DIP Switch timer delay settings.

For 56- applications using the optional 53- latchbolt monitor switch (53-56-), pin 5 of the 8-pin ElectroLynx connector
will be either an NO contact or NC contact depending on the position of the DIP switches on the motor controller faceplate.

5. Configuration Instructions DIP Switch Settings (for 53- and timer duration)

Fig. 19 DIP Switch Setting

for 53- Latch bolt Monitoring

Fig. 20 alternate DIP

Switch Setting (53- NC)

Fig. 21 Timer Delay Settings

(Default = 5 Seconds)

0 Seconds

2 Seconds

3 Seconds

4 Seconds

5 Seconds

10 Seconds

15 Seconds

20 Seconds