56- Electric Latch Retraction Exit Devices

Installation and Wiring Instructions

With Optional 53- Latchbolt; 55- Request to Exit;

and TL- (SARGuide) Connection Instructions

FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com

7. Wire Locations and Positions

56- Electric Latch Retraction devices are supplied with one 4-pin and one 8-pin Molex® connector.
Molex connectors allow simple installation using the ASSA ABLOY ElectroLynx® system.

8-pin Molex

Fig. 2 Wire Color and Position

1 - Black (56- 0VDC)
2 - Red (56- +24VDC)
3 - White (53- C)
4 - Green (EG)
5 - Orange (53- NC/NO)*
6 - Blue (55- C)
7 - Brown (55- NO)
8 - Yellow (55- NC)

1 - Violet (TL- Prefix is an option)
2 - Grey (TL+ Prefix is an option)
3 - Pink (56- Timer A)
4 - Tan (56- Timer B)

*NO/NC (Normally Open/Normally Closed)
is selectable on controller (refer to 53- DIP
switch instructions section III, part 5).

Factory preset is NO.

Without Timer

With Timer

Application

Wires

Recommended Hinge

Wires

Recommended Hinge

56-

3 wires

QC8

5 wires

QC12

53- 56-

5 wires

QC8

7 wires

QC12

55- 56-

6 wires

QC8

8 wires

QC12

53- 55- 56-

8 wires

QC8

10 wires

QC12

TL-56-

5 wires

QC12

7 wires

QC12

TL-53- 56-

7 wires

QC12

9 wires

QC12

TL-55- 56-

8 wires

QC12

10 wires

QC12

TL-53- 55- 56-

10 wires

QC12

12 wires

QC12

5. Hinge Requirements

Total

One-Way

Length of

Wire Run (ft)

Load Current @ 24VDC

1/4A

1/2A

3/4A

*1A

1-1/4A

1-1/2A

2A

3A

100

24

20

18

18

16

16

14

12

150

22

18

16

16

14

14

12

10

200

20

18

16

14

14

12

12

10

250

18

16

14

14

12

12

12

10

300

18

16

14

12

12

12

10

400

18

14

12

12

10

10

500

16

14

12

10

10

750

14

12

10

10

1,000

14

10

10

1,500

12

10

6. Wire Gauge Chart

*When calculating voltage drop, use 1A as the
recommended current draw for the 56- ELR.