Timer mode wiring, Timer mode installation instructions (continued) – SARGENT 56 - Latch Retraction User Manual

Page 9

Advertising
background image

A7925D 9

06/09/11

Copyright © 2009 Sargen

t Manufacturing Company

, an A

SS

A AB

LO

Y G

roup company

. All right

s reser

ved

.

Reproductions in whole or in par

t without express writ

ten permission of Sargen

t Manufacturing Company is prohibited

.

56- Electric Latch Retraction Exit Devices

Installation and Wiring Instructions

With Optional 53- Latchbolt; 55- Request to Exit;

and TL- (SARGuide) Connection Instructions

FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com

2. TIMER MODE Wiring

ElectroLynx Opening Installation

This is the simplest installation method, requiring the installer to plug the ElectroLynx
connectors from the exit device to the harness to the hinge and then to the pigtail,
which is connected to the access control system.

Requirements

56- Exit device

3” ElectroLynx connector harness (not supplied with 56- device)

McKinney QC ElectroLynx hinge (type of hinge depends on the application)

ElectroLynx door

1 - Violet (TL- Prefix is an option)
2 - Grey (TL+ Prefix is an option)
3 - Pink (56- Timer A)
4 - Tan (56- Timer B)

1. TIMER MODE Installation Instructions (continued)

4. Connect the ElectroLynx harness to the hinge:
a. Plug the door harness’s 8-pin and 4-pin connectors into the hinge’s ElectroLynx connector.
b. Secure the electric hinge to door.
Notes: Make sure no wires are pinched or damaged in the process.
Refer to detailed wiring instructions under

TIMER MODE wiring.

5. Apply 24V according to 56- input requirements:
Confirm that the LED is blinking and close the timer input circuit to retract the device. When the system retracts electrically,
confirm that it fully unlocks and that all bolts clear the strikes. Troubleshoot the device if issues are observed using the
steps outlined at the end of the

TIMER MODE section.

6. Store excess wiring under end cap and assemble with provided screws. Avoid pinching wires.

1 - Black (56- 0VDC)
2 - Red (56- +24VDC)
3 - White (53- C)
4 - Green (EG)
5 - Orange (53- NC/NO)*
6 - Blue (55- C)
7 - Brown (55- NO)
8 - Yellow (55- NC)

*NO/NC (Normally Open/Normally Closed)
is selectable on controller (refer to 53- DIP
switch instructions in this section, number 5).

Factory preset is NO.

Fig. 16 ElectroLynx

TIMER MODE

Wiring

3” ElectroLynx harness

with 8-and 4-pin connectors

(purchased separately)

8-pin F

8-pin M

8-pin M

4-pin F

4-pin M

4-pin M

Advertising
This manual is related to the following products: