Operator’s manual – Great Plains DICKEY-john Auto Section Control User Manual

Page 33

Advertising
background image

OPERATOR’S MANUAL

Auto Section Control System

11001-1561B-201207

FIELD PREPARATION / 31

IMPORTANT FUNCTIONALITY NOTES

The below situations can effect how Run In/Run Out functionality operates

in the field. Take into account the following when determining what values

to enter on the System Setup screen.

• A Run In/Run Out value of “0” turns on and off sections as soon as the

planter rows reach an area equal to 50% of the programmed row

spacing entered on the IntelliAg PDC setup of Row I/O. Example: If the

row spacing is set at 30” a Run In value of “0” will initiate shutoff of the

planter row 15” before reaching the first inner row of the headland. A

Run In value of “15” will initiate shutoff of the planter row at the first

inner row of the headland.

• To ensure the correct Run In/Run Out settings are entered, dig and

locate seed within the furrow and then measure distance from last

seed planted in row to desired shutoff point at headland. Mechanical

delays associated with the planter (chains, drives, hydraulics) can

have a direct impact on the row unit stopped versus the last seed

placed in the furrow.

• A side-to-side overlap adjustment percentage from 50% to 100% can

be changed during operation to increase or decrease the amount of

overlap. The steeper the angle, the greater the overlap percentage

should be to minimize gap.

• Population rate can also affect Run In/Run Out accuracy. This should

be accounted for when determining Run In/Run out values due to

meter speed ramp down time, i.e., higher population requires higher

meter RPM so it can take a fraction of a second longer for seed

placement to stop compared to a lower population and meter speed.

• Do not adjust the GPS lag value to compensate for shutting off and

turning on row units.

• When using a WAAS only signal, that has +/-12” accuracy, GPS

position drift may affect shutoff points. This drift can effect how the

Auto Section Control terminal identifies planter position as it relates to

turning rows on and off outside.

• Rows can unexpectedly turn on or off due to drift while driving or the

inaccuracy of the WAAS signal on pass-to-pass and headlands can

shift in and out over time due to the inaccuracy of the WAAS signal.

Advertising