Carrier WEATHER MASTER 48P2 User Manual

Page 32

Advertising
background image

32

Step 9 — Install Outdoor Hoods (Units without
Optional High-Capacity Power Exhaust)

UNIT SIZES 030-050
25% Outdoor-Air Hoods (Units without Economizer

Option) (Fig. 28)

1. Outdoor-air hoods are shipped bolted to the unit in a ship-

ping position. Remove the 6 screws holding each 25%

outdoor air hood shipping cover in place.

2. Remove the holddown screw from each upper corner of

each hood.

3. Pivot hoods outward (2 hoods).
4. Install 17 screws around outside of each hood. (Screws

are in the fastener package taped to the basepan inside the

fan section.)

5. Apply a bead of RTV or similar sealant to corner of each

hood at pivot points to prevent water leaks. See Fig. 29.

Economizer Hoods (Units with Economizer Option)

(Fig. 30 and 31)

1. Remove the 4 screws holding each of the 2 economizer

side hoods in place.

2. Pivot hoods outwards (2 hoods).
3. Apply seal strip to vertical flange of hood sides.
4. Install hood sides of hood top using 19 screws (7 each

side, 5 top). Screws are in fastener package located with

the hood sides and seal strip which is taped inside the

unit.

5. Apply a bead of RTV or similar sealant to corners of

economizer hoods at pivot points to prevent water leaks.

See Fig. 29.

UNIT SIZES 055-100
25% Outdoor-Air Hoods (Fig. 32) — The outdoor-air hoods

are factory installed on the 055-100 units.
Economizer Hoods (Units with Economizer Option) (Fig. 33-35)

1. Remove the 6 screws holding each of the 4 economizer

shipping covers in place.

2. Remove the holddown screw from each upper corner of

each economizer hood.

3. Pivot hoods outward (4 hoods).
4. Apply seal strip to vertical flange of hood sides.
5. Install 18 screws (5 each side, 6 top, and 2 bottom)

around the outside of each hood. (Screws are in the fas-

tener package taped to the basepan inside the fan section.)

6. Apply a bead of RTV or similar sealant to corner of econ-

omizer hood at pivot points to prevent water leaks. See

Fig. 29.

16-GAGE METAL
SEAL PLATE
(FIELD SUPPLIED
FIELD INSTALLED)

BOTTOM OF
BASE RAIL

Fig. 27 — Secondary Drain Seal Plate

Location (Slab Mount)

a48-8459

RTV

(ALL HOODS)

4”

OUTDOOR-AIR HOOD

Fig. 29 — Outdoor-Air and Economizer Hood

OUTDOOR
AIR HOOD

OUTDOOR
AIR HOOD

Fig. 28 — Outdoor Air Hood Installation

(Sizes 030-050)

SIDE HOOD
(ROTATE
OPEN)

SIDE HOOD
(ROTATE
OPEN)

END HOOD
(FIXED)

Fig. 30 — Economizer Outdoor-Air Hood

Installation (Sizes 030-050)

POWER EXHAUST (FIXED)

SIDE HOOD
(ROTATE
OPEN)

SIDE HOOD
(ROTATE
OPEN)

END HOOD
(FIXED)

Fig. 31 — Economizer with Power Exhaust

Outdoor-Air Hood Installation (Sizes 030-050)

a48-8461

Advertising