SMOKE PURGE — Smoke Purge mode removes smoke

from the interior spaces and replaces it with fresh outside air.

The factory-installed optional economizer with option/

accessory power exhaust are required for this function. Smoke

purge is accomplished by the following:
• turning supply fan on

• opening the economizer (option required)

• running the exhaust fans (option or accessory required)

• opening the exhaust dampers

See Fig. 82 for wiring.

SMOKE CONTROL INSTALLATION — Implementation of

the various smoke control modes on these units requires the in-

staller to modify the unit wiring to add contacts (via either

manual switches or relays) that will selectively interrupt and

override standard factory control sequences. See Table 31 and

Fig. 81 and 82 for more information.

Table 31 — Smoke Control Modes

LEGEND

*Power exhaust option required for this mode.

†Applicable to VAV units with appropriate options.

Fig. 86 — Open System Network Wiring

Fig. 86 — BT485 Installation

FUNCTION

MODE

Fire

Shutdown

Pressur-

ization

Evacuation*

Smoke
Purge*

Supply Fan

Off

On

Off

On

VFD†

Open/On

Open/On

Economizer

Closed

Open

Open

Open

Return Air
Damper

Open

Closed

Closed

Closed

Exhaust
Fans

Off

Off

On

On

Exhaust
Damper

Closed

Closed

Open

Open

VAV

Variable Air Volume

VFD

Variable Frequency Drive