Carrier WEATHER MASTER 48P2 User Manual
Page 49
49
Table 17 — Electrical Data — 48P2,P3,P4,P5075 Standard Units
LEGEND
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
VOLTAGE
3 PH, 60 Hz
VOLTAGE
RANGE
COMPRESSOR
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER
EXHAUST
POWER SUPPLY
No. A1,A2
No. B1,B2
Min
Max
Qty
RLA
(ea)
LRA
(ea)
Qty
RLA
(ea)
LRA
(ea)
Qty
FLA
Hp
FLA
Qty
Hp
(ea)
FLA
(ea)
MCA
FUSE OR
HACR BRKR*
460
414
508
2
26.9
179
2
26.9
179
4
3.3
(ea)
30
40.0
—
—
—
170.8
200
2
5.0
7.6
186.0
225
2
7.5
11.0
192.8
225
2
10.0
14.0
198.8
225
40
52.0
—
—
—
185.8
225
2
5.0
7.6
201.0
250
2
7.5
11.0
207.8
250
2
10.0
14.0
213.8
250
50
65.0
—
—
—
202.1
250
2
5.0
7.6
217.3
250
2
7.5
11.0
224.1
250
2
10.0
14.0
230.1
250
60
77.0
—
—
—
217.1
250
2
5.0
7.6
232.3
300
2
7.5
11.0
239.1
300
2
10.0
14.0
245.1
300
75
96.0
—
—
—
240.8
300
2
5.0
7.6
256.0
350
2
7.5
11.0
262.8
350
2
10.0
14.0
268.8
350
575
518
632
2
23.7
132
2
23.7
132
4
2.6
(ea)
30
32.0
—
—
—
145.2
175
2
5.0
6.1
157.4
175
2
7.5
9.0
163.2
175
2
10.0
11.0
167.2
175
40
41.0
—
—
—
156.5
175
2
5.0
6.1
168.7
200
2
7.5
9.0
174.5
200
2
10.0
11.0
178.5
200
50
52.0
—
—
—
170.2
200
2
5.0
6.1
182.4
225
2
7.5
9.0
188.2
225
2
10.0
11.0
192.2
225
60
62.0
—
—
—
182.7
225
2
5.0
6.1
194.9
250
2
7.5
9.0
200.7
250
2
10.0
11.0
204.7
250
75
77.0
—
—
—
201.5
250
2
5.0
6.1
213.7
250
2
7.5
9.0
219.5
250
2
10.0
11.0
223.5
300
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Nominal Horsepower
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps (for wire sizing)
RLA
— Rated Load Amps