Carrier WEATHER MASTER 48P2 User Manual

Page 49

Advertising
background image

49

Table 17 — Electrical Data — 48P2,P3,P4,P5075 Standard Units

LEGEND

* Used to determine minimum disconnect per NEC (National Electrical Code).

NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.

VOLTAGE

3 PH, 60 Hz

VOLTAGE

RANGE

COMPRESSOR

CONDENSER

FAN MOTOR

EVAPORATOR

FAN MOTOR

POWER

EXHAUST

POWER SUPPLY

No. A1,A2

No. B1,B2

Min

Max

Qty

RLA

(ea)

LRA

(ea)

Qty

RLA

(ea)

LRA

(ea)

Qty

FLA

Hp

FLA

Qty

Hp

(ea)

FLA

(ea)

MCA

FUSE OR

HACR BRKR*

460

414

508

2

26.9

179

2

26.9

179

4

3.3

(ea)

30

40.0

170.8

200

2

5.0

7.6

186.0

225

2

7.5

11.0

192.8

225

2

10.0

14.0

198.8

225

40

52.0

185.8

225

2

5.0

7.6

201.0

250

2

7.5

11.0

207.8

250

2

10.0

14.0

213.8

250

50

65.0

202.1

250

2

5.0

7.6

217.3

250

2

7.5

11.0

224.1

250

2

10.0

14.0

230.1

250

60

77.0

217.1

250

2

5.0

7.6

232.3

300

2

7.5

11.0

239.1

300

2

10.0

14.0

245.1

300

75

96.0

240.8

300

2

5.0

7.6

256.0

350

2

7.5

11.0

262.8

350

2

10.0

14.0

268.8

350

575

518

632

2

23.7

132

2

23.7

132

4

2.6

(ea)

30

32.0

145.2

175

2

5.0

6.1

157.4

175

2

7.5

9.0

163.2

175

2

10.0

11.0

167.2

175

40

41.0

156.5

175

2

5.0

6.1

168.7

200

2

7.5

9.0

174.5

200

2

10.0

11.0

178.5

200

50

52.0

170.2

200

2

5.0

6.1

182.4

225

2

7.5

9.0

188.2

225

2

10.0

11.0

192.2

225

60

62.0

182.7

225

2

5.0

6.1

194.9

250

2

7.5

9.0

200.7

250

2

10.0

11.0

204.7

250

75

77.0

201.5

250

2

5.0

6.1

213.7

250

2

7.5

9.0

219.5

250

2

10.0

11.0

223.5

300

FLA

Full Load Amps

HACR — Heating, Air Conditioning, and Refrigeration
Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

RLA

Rated Load Amps