Step 20 — Install Optional Motormaster

®

V

Control —

The Motormaster V control is a motor speed

control device which adjusts condenser fan motor speed in re-

sponse to varying liquid refrigerant pressure. A properly applied

Motormaster V control extends the operating range of air-condi-

tioning systems and permits operation at lower outdoor ambient

temperatures.

The optional Motormaster V controls are factory-installed.

Field-fabricated and installed wind baffles are also required for

units in areas with prevailing winds of more than 5 mph and

where temperatures drop below 32 F. The Motormaster V con-

trol permits operation of the unit to an ambient temperature of

–20 F. The control regulates the speed of one or two 3-phase fan

motors depending on unit size. Replacement of the fan motor on

most units is not necessary.
INSTALL FIELD-FABRICATED WIND BAFFLES

On size 040-060 units, in areas with prevailing winds of

more than 5 mph and where temperatures drop below 32 F,

wind baffles must be field fabricated to ensure proper cooling

cycle operation at low-ambient temperatures with Motormaster

V controls. Wind baffles are not needed on size 030, 035, and

070-100 units. See Fig. 70 for baffle details. Use 20-gage galva-

nized sheet metal, or similar corrosion-resistant material for the

baffles. Use field-supplied screws to attach baffles to unit.

Screws should be

1

/

4

-in. diameter or larger. Screws should not

be more than

1

/

2

-inch in length. Drill required screw holes for

mounting baffles.

THERMISTOR

PIN

CONNECTION

POINT

FUNCTION AND LOCATION

PART NO.

Thermistors

SAT1

J8 – 1,2 (SGC)

Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)

HH79NZ033

SAT2

J8 – 3,4 (SGC)

Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)

SAT3

J8 – 5,6 (SGC)

Supply-Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided,
field-installed)

LIMTTEMP

J8 – 15,16 (SGC)

Limit Switch Thermistor (LIMTTEMP) — Inserted next the
lower limit switch (factory-installed)

INLET
HOOD

INLET HOOD
SIDE

INLET HOOD
SIDE

SCREEN
(WITH SPEED CLIPS)

a48-8473

Fig. 67 — Inlet Hood Assembly (30-in.)

Fig. 68 — Air Baffle (14-in.)

Fig. 69 — Air Baffle (30-in.)

a48-8591

a48-8590

WARNING

To avoid the possibility of electrical shock, open all discon-

nects before installing or servicing this accessory.

CAUTION

To avoid damage to refrigerant coils, electrical compo-

nents, and wiring use extreme care when drilling screw

holes and screwing in fasteners.