Table 30 — Open System Wiring Specifications and Recommended Vendors

LEGEND

This allows the space to be overpressurized relative to adjacent

zones and prevents or slows entry of smoke into this space

from adjacent zones. See Fig. 82 for wiring.
EVACUATION — Evacuation mode removes smoke or un-

desirable air from interior spaces without reintroducing unsuit-

able air. The factory-installed optional economizer with option/

accessory power exhaust is required for this function. Evacua-

tion is accomplished by the following:
• turning the supply fan off

• opening the economizer (option required)

• running the exhaust fans (option or accessory required)

• opening the exhaust dampers.
See Fig. 82 for wiring.

WIRING SPECIFICATIONS

RECOMMENDED VENDORS AND PART NUMBERS

Wire Type

Description

Connect Air

International

Belden

RMCORP

Contractors

Wire and Cable

MS/TP

Network (RS-485)

22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.

W221P-22227

25160PV

CLP0520LC

24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.

W241P-2000F

82841

25120-OR

Rnet

4 conductor, unshielded, CMP, 18 AWG, plenum rated.

W184C-2099BLB

6302UE

21450

CLP0442

AWG

American Wire Gage

CL2P

Class 2 Plenum Cable

CMP

Communications Plenum Rated

FEP

Fluorinated Ethylene Polymer

TC

Tinned Copper

8

7

6

5

4

3

2

1

09

8

7

6

5

4

3

2

1

09

BACNET
BAUD RATE
DIP SWITCHES

ADDRESS
ROTARY
SWITCHES

POWER LED

RUN LED

ERROR LED

BACNET
CONNECTION

BT485
TERMINATOR

Tx2 LED

Rx2 LED

Tx1 LED

Rx1 LED

Fig. 85 — UPC Open Controller