Table 24 — Electrical Data — 48P2,P3,P4,P5100 Units with Optional High-Capacity Power Exhaust

LEGEND

* Used to determine minimum disconnect per NEC (National Electrical Code).

NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.

VOLTAGE

3 PH, 60 Hz

VOLTAGE

RANGE

COMPRESSOR

CONDENSER

FAN MOTOR

EVAPORATOR

FAN MOTOR

POWER EXHAUST

POWER SUPPLY

No. A1

No. B1

Min

Max

Qty

RLA

(ea)

LRA

(ea)

Qty

RLA

(ea)

LRA

(ea)

Qty

FLA

Hp

FLA

Qty

Hp

(ea)

FLA

(ea)

MCA

FUSE OR HACR

BRKR*

460

414

508

3

23.1

150

3

26.9

179

6

3.3

(ea)

30

40.0

2

10

14.0

247.8

250

2

15

21.0

261.8

300

2

20

27.0

273.8

300

2

25

34.0

287.8

300

2

30

40.0

299.8

300

40

52.0

2

10

14.0

262.8

300

2

15

21.0

276.8

300

2

20

27.0

288.8

300

2

25

34.0

302.8

350

2

30

40.0

314.8

350

50

65.0

2

10

14.0

279.1

300

2

15

21.0

293.1

350

2

20

27.0

305.1

350

2

25

34.0

319.1

350

2

30

40.0

331.1

350

60

77.0

2

10

14.0

294.1

350

2

15

21.0

308.1

350

2

20

27.0

320.1

350

2

25

34.0

334.1

400

2

30

40.0

346.1

400

75

96.0

2

10

14.0

317.8

400

2

15

21.0

331.8

400

2

20

27.0

343.8

400

2

25

34.0

357.8

450

2

30

40.0

369.8

450

575

518

632

3

19.9

109

3

23.7

132

6

2.6

(ea)

30

32.0

2

10

11.0

208.4

225

2

15

17.0

220.4

250

2

20

22.0

230.4

250

2

25

27.0

240.4

250

2

30

32.0

250.4

300

40

41.0

2

10

11.0

219.7

250

2

15

17.0

231.7

250

2

20

22.0

241.7

250

2

25

27.0

251.7

300

2

30

32.0

261.7

300

50

52.0

2

10

11.0

233.4

250

2

15

17.0

245.4

250

2

20

22.0

255.4

300

2

25

27.0

265.4

300

2

30

32.0

275.4

300

60

62.0

2

10

11.0

245.9

300

2

15

17.0

257.9

300

2

20

22.0

267.9

300

2

25

27.0

277.9

300

2

30

32.0

287.9

300

75

77.0

2

10

11.0

264.7

300

2

15

17.0

276.7

350

2

20

22.0

286.7

350

2

25

27.0

296.7

350

2

30

32.0

306.7

350

FLA

Full Load Amps

HACR —

Heating, Air Conditioning, and Refrigeration

Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

RLA

Rated Load Amps