Carrier WEATHER MASTER 48P2 User Manual

Page 45

Advertising
background image

45

Table 13 — Electrical Data, 48P2,P3,P4,P5050 Units (cont)

LEGEND

* Used to determine minimum disconnect per NEC (National Electrical Code).

NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.

VOLTAGE

3 PH, 60 Hz

VOLTAGE

RANGE

COMPRESSOR

CONDENSER

FAN MOTOR

EVAPORATOR

FAN MOTOR

POWER EXHAUST

POWER SUPPLY

No. A1

No. B1

Min

Max

Qty

RLA

(ea)

LRA

(ea)

Qty

RLA

(ea)

LRA

(ea)

Qty

FLA

Hp

FLA

Qty

Hp

(ea)

FLA

(ea)

MCA

FUSE OR

HACR BRKR*

575

518

632

2

12.8

80

2

14.7

100

4

2.6

(ea)

7

1

/

2

9.0

78.1

90

2

3

3.9

85.9

100

2

5

6.1

90.3

100

2

7.5

9.0

96.1

110

2

10

11.0

100.1

110

10

11.0

80.1

90

2

3

3.9

87.9

100

2

5

6.1

92.3

100

2

7.5

9.0

98.1

110

2

10

11.0

102.1

110

15

17.0

86.7

100

2

3

3.9

94.5

110

2

5

6.1

98.9

110

2

7.5

9.0

104.7

110

2

10

11.0

108.7

125

20

22.0

92.9

110

2

3

3.9

100.7

110

2

5

6.1

105.1

125

2

7.5

9.0

110.9

125

2

10

11.0

114.9

125

25

27.0

99.2

125

2

3

3.9

107.0

125

2

5

6.1

111.4

125

2

7.5

9.0

117.2

125

2

10

11.0

121.2

125

30

32.0

105.4

125

2

3

3.9

113.2

125

2

5

6.1

117.6

125

2

7.5

9.0

123.4

150

2

10

11.0

127.4

150

FLA

Full Load Amps

HACR — Heating, Air Conditioning, and Refrigeration
Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

RLA

Rated Load Amps

Advertising
This manual is related to the following products: