61

After removing all shipping brackets, level the fan using the

adjustment screws. On all 4 corners the dimension from cross

rail to fan sled should be as shown in Fig. 52.

Step 16 — Connect Gas Piping —

Unit is

equipped for use with natural gas only. Installation must con-

form with local building codes, or in the absence of local

codes, with the National Fuel Gas Code (NFGC), ANSI

Z223.1.

A

1

/

8

-in. NPT tapping plug, accessible for test gage connec-

tion, must be field installed immediately upstream of gas sup-

ply connection to unit, but after manual gas valve. See Fig. 53.

Natural gas pressure at unit gas connection must not be less

than 5 in. wg or greater than 13 in. wg.

Size gas supply piping for 0.5 in. wg maximum pressure

drop. Do not use supply pipe smaller than unit gas connection.

Step 17 — Configure Optional Staged Gas
or Modulating Gas Control —

The 48P Series large

rooftop units may be ordered with an optional factory-installed

staged gas or modulating gas control system that monitors

heating operation of the rooftop.

Refer to the Unit Controls and Troubleshooting book for in-

formation on configuring staged gas or modulating gas control.

Fig. 51 — Shipping Brackets (Sizes 075-100)

a48-8468

Fig. 52 — Optional Return

Fan Shipping Brackets

NOTE: All dimensions are in inches.

CAUTION

Disconnect gas piping from unit when leak testing at pres-

sures greater than 0.5 psig. Pressures greater than 0.5 psig

will cause gas valve damage resulting in a hazardous con-

dition. If gas valve is subjected to pressure greater than

0.5 psig, it must be replaced.