Carrier Comfort Network

®

(CCN) Interface —

The 48P Series units can be connected to the CCN system if

desired. The communication bus wiring is supplied and

installed in the field. It consists of shielded, 3-conductor cable

with shield wire.

The system elements are connected to the communication

bus in a daisy chain arrangement. The positive pin of each

system element communication connector must be wired to the

positive pins of the system element on either side of it, the

negative pins must be wired to the negative pins, and the signal

pins must be wired to common pins. Wiring connections for

the CCN system should be made at the terminal block using the

screw terminals. The board also contains an RJ14 CCN plug

that can be used to connect a field service computer. There is

also another RJ14 LEN (Local Equipment Network) connec-

tion that is used to download software or connect a Naviga-

tor™ device.
NOTE: Conductors and drain wire must be 20 AWG minimum

stranded, tinned copper. Individual conductors must be insu-

lated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An

aluminum/polyester 100% foil shield and an outer jacket of

PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum

operating temperature range of –4 to 140 F (–20 C to 60 C) is

required. See Table 28 for cables that meet the requirements.

Table 28 — CCN Connection Approved

Shielded Cables

The following color code is recommended:

NOTE: If a cable with a different color scheme is selected, a

similar color code should be adopted for the entire network.

At each system element, the shields of its communication

bus cables must be tied together. If the communication bus is

entirely within one building, the resulting continuous field

must be connected to a ground at one point only. If the commu-

nication bus cable exits from one building and enters another,

the shields must be connected to grounds at the lightning

suppressor in each building where the cable enters or exits the

building (one point per building only).
To connect the unit to the network (Fig. 84):

1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white

(common) and black (–) conductors. (If a different net-

work color scheme is used, substitute appropriate colors.)

3. Wire the CCN to the screw terminals on the COMM

board as follows (Fig. 84):

a. Secure the red (+) wire to CCN screw terminal +

on the COMM board.

b. Secure the white (common) wire to CCN screw

terminal C on the COMM board.

TB201

MBB

J5

Fig. 84 — CCN Connections

a48-8487

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

IMPORTANT: When connecting the CCN communica-

tion bus to a system element, use a color coding system for

the entire network to simplify installation and checkout.

SIGNAL

TYPE

CCN BUS CONDUCTOR

INSULATION COLOR

COMM1 PLUG

PIN NO.

+

RED

1

COMMON

WHITE

2

BLACK

3