Table 1A — Physical Data 48P2,P3,P4,P5030-050 (cont)

LEGEND

* 460-3-60 only.
†See Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.

BASE UNIT

48P2,P3,P4,P5040

48P2,P3,P4,P5050

NOMINAL CAPACITY (tons)

40

50

OPERATING WEIGHT (lb)

Standard Chassis

Extended Chassis

Standard Chassis

Extended Chassis

Base Unit

Low Heat

5810

6310

6025

6525

High Heat

5940

6440

6155

6655

With Economizer

Low Heat

6110

6610

6325

6825

High Heat

6240

6740

6455

6955

COMPRESSORS

Scroll

Quantity...Type

2...ZP103/1...ZP182

2...ZP120/2...ZP137

Oil Charge (oz) per Compressor

110

110

Number of Refrigerant Circuits

2

2

REFRIGERANT

R-410A

Operating Charge (lb), Ckt 1/Ckt 2

Standard Evaporator Coil

21.6/26.7

29.4/29.0

Standard Evaporator with Humidi-MiZer®

21.6/39.1

29.4/41.4

Alternate High-Capacity Evaporator Coil

35.1/37.2

38.2/36.5

Alternate High-Capacity Evaporator with Humidi-MiZer

31.1/49.6

38.2/48.9

CONDENSER COILS

Aluminum Novation® Heat Exchanger with Microchannel Coils

Quantity

2

2

Total Face Area (sq ft)

66.7

66.7

EVAPORATOR COILS

Quantity

1

Total Face Area (sq ft)

45.5

Refrigerant Feed Device...No. per Circuit

TXV...2

Standard Evaporator Coils

Rows...Fins/in.

3...15.0

4...15.0

Fin Type

Double Wavy

Double Wavy

Tube Type

Cross Hatched

Cross Hatched

Alternate, High-Capacity Evaporator Coils

Rows...Fins/in.

6...16.0

6...16.0

Fin Type

Double Wavy

Double Wavy

Tube Type

Cross Hatched

Cross Hatched

HEATING SECTION

Low Heat

High Heat

Low Heat

High Heat

Number of Heat Exchangers

7

14

7

14

Input (MBtuh)

325

650

325

650

Output (MBtuh) (Vertical/Horizontal)

263/260

527/520

263/260

527/520

Temperature Rise Range (F)

10-40

25-55

10-40

25-55

Efficiency (%) (Vertical/Horizontal)

81/80

81/80

81/80

81/80

Burner Orifice Diameter

Quantity (in. ...drill no.)

7 (.1285...30)

14 (.1285...30)

7 (.1285...30)

14 (.1285...30)

Manifold Pressure (in. wg)

3.5

3.5

3.5

3.5

Line Pressure (in. wg) (min...max)

5.0...13.0

5.0...13.0

5.0...13.0

5.0...13.0

Firing Stages

2

2

2

2

Number of Gas Valves

1

2

1

2

CONDENSER FANS

Propeller Type

Quantity...Diameter (in.)

3...30

4...30

Nominal Cfm

30,000

38,000

Motor Hp...Rpm

1.0...1140

1.0...1140

SUPPLY FAN

Centrifugal 25 x 25 in.

Nominal Cfm

14,000

14,000

Maximum Allowable Cfm

20,000

20,000

Maximum Allowable Rpm

900

900

Shaft Diameter at Pulley (in.)

1

11

/

16

1

11

/

16

SUPPLY-FAN MOTOR AND DRIVE

(Any motor available on any unit)

Motor Hp

7.5

10

15

20

25

30*

Motor Frame Size

213T

215T

254T

256T

284T

286T

Efficiency at Full Load (%)

High Efficiency

88.5

89.5

91.0

91.0

91.7

92.4

Premium Efficiency

91.7

91.7

93.0 93.6

93.6

93.6

Fan Pulley Pitch Diameter (in.)

13.7

13.7

13.7

13.7

13.7

12.5

Motor Pulley Pitch Diameter (in.)

3.4

4.3

4.9

5.5

6.5

6.5

Resulting Fan Speed (rpm)

438

549

626

703

830 910

Belts Quantity...Type

2...BX60

2...5VX630

2...5VX630

2...5VX630

2...5VX650

3...5VX630

Center Distance Range (in.)

17.74-14.30

17.74-14.30

17.63...14.01

17.63...14.01

16.63...12.87

16.63...12.87

OPTIONAL POWER EXHAUST†

Centrifugal, 18 x 15 in. (Any motor available on any unit)

Quantity...Motor Hp

2...3.0

2...5.0

2...7.5

2...10

Motor Frame Size

High Eff

56HZ

184T

213T

215T

Prem Eff

182T

184T

213T

215T

Efficiency at Full Load (%) High/Premium

81.0/88.5

87.5/89.5

88.5/91.7

89.5/91.7

Fan Pulley Pitch Diameter (in.)

High Eff

11

10.4

12

12

Prem Eff

11.0

10.4

12

12

Motor Pulley Pitch Diameter Range (in.)

High Eff

4.1-3.1

4.7-3.7

6.0-4.8

7.0-5.8

Prem Eff

4.1-3.1

4.7-3.7

6.0-4.8

7.0-5.8

Motor Pulley Pitch Diameter Factory Setup (in.)

4.1

4.2

5.4

6.4

Blower Shaft Diameter at Pulley (in.)

1

7

/

16

1

7

/

16

1

7

/

16

1

7

/

16

Fan Rpm Range

500-656

621-785

717-882

854-1000

Factory Setup Fan Rpm

656

703

800

927

Maximum Allowable Rpm

1000

1000

1000

1000

FILTERS

Standard Efficiency Throwaway (Standard)

Quantity...Size (in.)

8...20 x 25 x 2, 8...20 x 20 x 2

8...20 x 25 x 2, 8...20 x 20 x 2

Medium Efficiency (30%) Pleated (Optional)

Quantity...Size (in.)

8...20 x 25 x 2, 8...20 x 20 x 2

8...20 x 25 x 2, 8...20 x 20 x 2

High Efficiency (90%) Bag Filters

with High Velocity Prefilters (Opt)

Quantity...Size (in.)

Bag Filter

6...20 x 24 x 22, 6...20 x 20 x 22

6...20 x 24 x 22, 6...20 x 20 x 22

Prefilter

12...16 x 20 x 2, 3...20 x 24 x 2

12...16 x 20 x 2, 3...20 x 24 x 2

MERV 15 Cartridge Filters with High Velocity Prefilters (Opt)

Quantity...Size (in.)

Cartridge Filter

6...20 x 24 x 12, 6...20 x 20 x 12

6...20 x 24 x 12, 6...20 x 20 x 12

Prefilter

12...16 x 20 x 2, 3...20 x 24 x 2

12...16 x 20 x 2, 3...20 x 24 x 2

OUTSIDE AIR SCREENS

Standard Hood (25%) Quantity...Size (in.)

None

None

OPTIONAL ECONOMIZER FILTER

Aluminum Frame, Permanent

Quantity...Size (in.)

5...20 x 20 x 2
2...20 x 25 x 1

5...20 x 20 x 1
2...20 x 25 x 1

MBtuh — Btuh in Thousands