Carrier WEATHER MASTER 48P2 User Manual

Page 47

Advertising
background image

47

Table 15 — Electrical Data, 48P2,P3,P4,P5060 Units

LEGEND

* Used to determine minimum disconnect per NEC (National Electrical Code).

NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.

VOLTAGE

3 PH, 60 Hz

VOLTAGE

RANGE

COMPRESSOR

CONDENSER

FAN MOTOR

EVAPORATOR

FAN MOTOR

POWER EXHAUST

POWER SUPPLY

No. A1

No. B1

Min

Max

Qty

RLA

(ea)

LRA

(ea)

Qty

RLA

(ea)

LRA

(ea)

Qty

FLA

Hp

FLA

Qty

Hp

(ea)

FLA

(ea)

MCA

FUSE OR

HACR BRKR*

208/230

187

253

2

51.3

300

2

51.3

300

4

6.6

(ea)

15

46.2/42.0

/

290.6/286.4

300/300

2

5.0 16.7 / 15.2

324.0/316.8

350/350

2

7.5 24.2 / 22.0

339.0/330.4

350/350

2

10.0 30.8 / 28.0

352.2/342.4

400/350

20

59.4/54.0

/

305.9/299.1

350/350

2

5.0 16.7 / 15.2

339.3/329.5

350/350

2

7.5 24.2 / 22.0

354.3/343.1

400/350

2

10.0 30.8 / 28.0

367.5/355.1

400/400

25

74.8/68.0

/

325.1/316.6

350/350

2

5.0 16.7 / 15.2

358.5/347.0

400/400

2

7.5 24.2 / 22.0

373.5/360.6

400/400

2

10.0 30.8 / 28.0

386.7/372.6

450/400

30

88.0/80.0

/

341.6/331.6

400/400

2

5.0 16.7 / 15.2

375.0/362.0

450/400

2

7.5 24.2 / 22.0

390.0/375.6

450/450

2

10.0 30.8 / 28.0

403.2/387.6

450/450

40

114.0/104.0

/

374.1/361.6

450/450

2

5.0 16.7 / 15.2

407.5/392.0

500/450

2

7.5 24.2 / 22.0

422.5/405.6

500/500

2

10.0 30.8 / 28.0

435.7/417.6

500/500

460

414

508

2

23.1

150

2

23.1

150

4

3.3

(ea)

15

21.0

132.4

150

2

5.0

7.6

147.6

150

2

7.5

11.0

154.4

175

2

10.0

14.0

160.4

175

20

27.0

139.4

150

2

5.0

7.6

154.6

175

2

7.5

11.0

161.4

175

2

10.0

14.0

167.4

175

25

34.0

148.1

175

2

5.0

7.6

163.3

175

2

7.5

11.0

170.1

200

2

10.0

14.0

176.1

200

30

40.0

155.6

175

2

5.0

7.6

170.8

200

2

7.5

11.0

177.6

200

2

10.0

14.0

183.6

200

40

52.0

170.6

200

2

5.0

7.6

185.8

225

2

7.5

11.0

192.6

225

2

10.0

14.0

198.6

250

575

518

632

2

19.9

109

2

19.9

109

4

2.6

(ea)

15

17.0

112.0

125

2

5.0

6.1

124.2

125

2

7.5

9.0

130.0

150

2

10.0

11.0

134.0

150

20

22.0

117.5

125

2

5.0

6.1

129.7

150

2

7.5

9.0

135.5

150

2

10.0

11.0

139.5

150

25

27.0

123.8

150

2

5.0

6.1

136.0

150

2

7.5

9.0

141.8

150

2

10.0

11.0

145.8

150

30

32.0

130.0

150

2

5.0

6.1

142.2

150

2

7.5

9.0

148.0

175

2

10.0

11.0

152.0

175

40

41.0

141.3

175

2

5.0

6.1

153.5

175

2

7.5

9.0

159.3

200

2

10.0

11.0

163.3

200

FLA

Full Load Amps

HACR — Heating, Air Conditioning, and Refrigeration
Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

RLA

Rated Load Amps

Advertising
This manual is related to the following products: