48
Table 16 — Electrical Data, 48P2,P3,P4,P5070 Units
LEGEND
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
VOLTAGE
3 PH, 60 Hz
VOLTAGE
RANGE
COMPRESSOR
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
Min
Max
Qty
RLA
(ea)
LRA
(ea)
Qty
RLA
(ea)
LRA
(ea)
Qty
FLA
Hp
FLA
Qty
Hp
(ea)
FLA
(ea)
MCA
FUSE OR
HACR BRKR*
208/230
187
253
2
51.3
300
2
55.8
340
4
6.6
(ea)
15
46.2/42.0
—
—
—
/
—
300.8/ 296.6
350/350
2
5.0 16.7 / 15.2
334.2/ 327.0
350/350
2
7.5 24.2 / 22.0
349.2/ 340.6
400/350
2
10.0 30.8 / 28.0
362.4/ 352.6
400/400
20
59.4/54.0
—
—
—
/
—
314.9/ 308.6
350/350
2
5.0 16.7 / 15.2
348.3/ 339.0
400/350
2
7.5 24.2 / 22.0
363.3/ 352.6
400/400
2
10.0 30.8 / 28.0
376.5/ 364.6
400/400
25
74.8/68.0
—
—
—
/
—
334.1/ 325.6
400/350
2
5.0 16.7 / 15.2
367.5/ 356.0
400/400
2
7.5 24.2 / 22.0
382.5/ 369.6
450/400
2
10.0 30.8 / 28.0
395.7/ 381.6
450/400
30
88.0/80.0
—
—
—
/
—
350.6/ 340.6
400/400
2
5.0 16.7 / 15.2
384.0/ 371.0
450/450
2
7.5 24.2 / 22.0
399.0/ 384.6
450/450
2
10.0 30.8 / 28.0
412.2/ 396.6
500/450
40
114.0/104.0
—
—
—
/
—
383.1/ 370.6
450/450
2
5.0 16.7 / 15.2
416.5/ 401.0
500/500
2
7.5 24.2 / 22.0
431.5/ 414.6
500/500
2
10.0 30.8 / 28.0
444.7/ 426.6
500/500
460
414
508
2
23.1
150
2
26.9
179
4
3.3
(ea)
15
21.0
—
—
—
140.9
150
2
5.0
7.6
156.1
175
2
7.5
11.0
162.9
175
2
10.0
14.0
168.9
175
20
27.0
—
—
—
147.0
150
2
5.0
7.6
162.2
175
2
7.5
11.0
169.0
175
2
10.0
14.0
175.0
200
25
34.0
—
—
—
155.7
175
2
5.0
7.6
170.9
200
2
7.5
11.0
177.7
200
2
10.0
14.0
183.7
200
30
40.0
—
—
—
163.2
200
2
5.0
7.6
178.4
200
2
7.5
11.0
185.2
225
2
10.0
14.0
191.2
225
40
52.0
—
—
—
178.2
225
2
5.0
7.6
193.4
225
2
7.5
11.0
200.2
250
2
10.0
14.0
206.2
250
575
518
632
2
19.9
109
2
23.7
132
4
2.6
(ea)
15
17.0
—
—
—
120.5
125
2
5.0
6.1
132.7
150
2
7.5
9.0
138.5
150
2
10.0
11.0
142.5
150
20
22.0
—
—
—
125.5
150
2
5.0
6.1
137.7
150
2
7.5
9.0
143.5
150
2
10.0
11.0
147.5
150
25
27.0
—
—
—
131.4
150
2
5.0
6.1
143.6
150
2
7.5
9.0
149.4
175
2
10.0
11.0
153.4
175
30
32.0
—
—
—
137.6
150
2
5.0
6.1
149.8
175
2
7.5
9.0
155.6
175
2
10.0
11.0
159.6
175
40
41.0
—
—
—
148.9
175
2
5.0
6.1
161.1
200
2
7.5
9.0
166.9
200
2
10.0
11.0
170.9
200
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Nominal Horsepower
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps (for wire sizing)
RLA
— Rated Load Amps