Table 14 — Electrical Data, 48P2,P3,P4,P5055 Units
LEGEND
* Used to determine minimum disconnect per NEC (National Electrical Code).
NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at
0.3 FLA each.
VOLTAGE
3 PH, 60 Hz
VOLTAGE
RANGE
COMPRESSOR
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER EXHAUST
POWER SUPPLY
No. A1
No. B1
Min
Max
Qty
RLA
(ea)
LRA
(ea)
Qty
RLA
(ea)
LRA
(ea)
Qty
FLA
Hp
FLA
Qty
Hp
(ea)
FLA
(ea)
MCA
FUSE OR
HACR BRKR*
208/230
187
253
2
48.1
245
2
48.1
245
4
6.6
(ea)
15
46.2/42.0
—
—
—
/
—
277.0/272.8
300/300
2
5.0 16.7 / 15.2
310.4/303.2
350/350
2
7.5 24.2 / 22.0
325.4/316.8
350/350
2
10.0 30.8 / 28.0
338.6/328.8
350/350
20
59.4/54.0
—
—
—
/
—
293.1/286.3
350/300
2
5.0 16.7 / 15.2
326.5/316.7
350/350
2
7.5 24.2 / 22.0
341.5/330.3
400/350
2
10.0 30.8 / 28.0
354.7/342.3
400/350
25
74.8/68.0
—
—
—
/
—
312.3/303.8
350/350
2
5.0 16.7 / 15.2
345.7/334.2
400/400
2
7.5 24.2 / 22.0
360.7/347.8
400/400
2
10.0 30.8 / 28.0
373.9/359.8
400/400
30
88.0/80.0
—
—
—
/
—
328.8/318.8
400/350
2
5.0 16.7 / 15.2
362.2/349.2
450/400
2
7.5 24.2 / 22.0
377.2/362.8
450/400
2
10.0 30.8 / 28.0
390.4/374.8
450/450
40
114.0/104.0
—
—
—
/
—
361.3/348.8
450/450
2
5.0 16.7 / 15.2
394.7/379.2
500/450
2
7.5 24.2 / 22.0
409.7/392.8
500/450
2
10.0 30.8 / 28.0
422.9/404.8
500/500
460
414
508
2
18.6
125
2
18.6
125
4
3.3
(ea)
15
21.0
—
—
—
113.9
125
2
5.0
7.6
129.1
150
2
7.5
11.0
135.9
150
2
10.0
14.0
141.9
150
20
27.0
—
—
—
121.4
125
2
5.0
7.6
136.6
150
2
7.5
11.0
143.4
150
2
10.0
14.0
149.4
175
25
34.0
—
—
—
130.1
150
2
5.0
7.6
145.3
175
2
7.5
11.0
152.1
175
2
10.0
14.0
158.1
175
30
40.0
—
—
—
137.6
175
2
5.0
7.6
152.8
175
2
7.5
11.0
159.6
175
2
10.0
14.0
165.6
200
40
52.0
—
—
—
152.6
200
2
5.0
7.6
167.8
200
2
7.5
11.0
174.6
225
2
10.0
14.0
180.6
225
575
518
632
2
14.7
100
2
14.7
100
4
2.6
(ea)
15
17.0
—
—
—
90.5
100
2
5.0
6.1
102.7
110
2
7.5
9.0
108.5
125
2
10.0
11.0
112.5
125
20
22.0
—
—
—
96.7
110
2
5.0
6.1
108.9
125
2
7.5
9.0
114.7
125
2
10.0
11.0
118.7
125
25
27.0
—
—
—
103.0
125
2
5.0
6.1
115.2
125
2
7.5
9.0
121.0
125
2
10.0
11.0
125.0
150
30
32.0
—
—
—
109.2
125
2
5.0
6.1
121.4
150
2
7.5
9.0
127.2
150
2
10.0
11.0
131.2
150
40
41.0
—
—
—
120.5
150
2
5.0
6.1
132.7
150
2
7.5
9.0
138.5
175
2
10.0
11.0
142.5
175
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Nominal Horsepower
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps (for wire sizing)
RLA
— Rated Load Amps