3-3 Cyclic communication

3-15

3

C

om
m

uni

ca

tin

g

w

ith FD

-M

H

Se
ries

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (FD-MH) -

„

Warning code list

No warning code occurs in the DL-EP1 and in the FD-MH Series sensor amplifiers
connected to the DL-EP1.

The data to the sensor amplifier is assigned to the OUT area of the EtherNet/IP
scanner.

„

External Input (5 Words (10 Bytes)) assembly instance (Instance ID): 65H

ID numbers (ID01 to ID10) are assigned for each sensor amplifier according to the

number of sensor amplifiers. The ID numbers larger than the number of connected

sensor amplifiers and ID11 to ID15 are not assigned.

Assignment to OUT Area (Scanner to DL-EP1)

DL-EP1 data

Scanner's OUT area

Address 0
Address 1

Address 9

External Input
(Assembly Instance: 101)

1-byte (8-bit) data

Name

Address

(Byte)

bit7

bit6

bit5

bit4

bit3

bit2

bit1

bit0

External

Input

Request 1

(Integration

Reset)

0

ID08

. . . . .

ID01

1

Reserved for

system

ID15

. . . . .

ID09

External

Input

Request 2

(Flow HOLD

Reset)

2

ID08

. . . . .

ID01

3

Reserved for

system

ID15

. . . . .

ID09

External

Input

Request 3

(Unassigned)

4

ID08

. . . . .

ID01

5

Reserved for

system

ID15

. . . . .

ID09

External

Input

Request 4

(Temperature

HOLD Reset)

6

ID08

. . . . .

ID01

7

Reserved for

system

ID15

. . . . .

ID09

External

Input

Request 5

(Unassigned)

8

ID08

. . . . .

ID01

9

Reserved for

system

ID15

. . . . .

ID09