background image

3-2 Device Maps

3-5

3

Co
mm

u

ni

c

a

ting
w

ith t
he FD

-S

s

er

ie

s

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -

Number [n] denotes the first relay number assigned to the DL-CL1.

*1

See

"Reading an Output from a Sensor Amplifier" (page 3-17).

*2

See

"Reading Current Values (Instantaneous Flow Rate) from Sensor Amplifiers" (page 3-18).

*3

See

"Reading/Writing Settings or Status of a Sensor Amplifier" (page 3-21).

See

"Issuing a Motion Command to a Sensor Amplifier" (page 3-20).

Remote Output RY (Master Station -> DL-CL1)

Operating

mode

Device no.

(HEX)

Name

Communication

method

Description

Reading range

Monitor mode

1

RX[n] + 53

Current
Value Update
Locked

-

This is output when current value update is
locked (current value update lock request (RY[n]
+ 53) is enabled).

0: Update
enabled
1: Update
locked

RX[n] + 54
to 5D

System
reserved

-

Unusable

RX[n] + 5E

Current value
page change
complete

*2

Used for reading the current value.This is output
when the current value page has been changed.

0->1: Change
complete

RX[n] + 5F

Current value
page change
error

*2

Used for reading the current value.This is output
if an error occurs while changing the current
value page.

0:No Error
1:Error

RX[n] + 60
to 63

(Not used)

-

-

-

RX[n] + 6F (Not used)

-

-

-

RX[n] + 1B

Remote ready

-

This is output when the DL-CL1 is correctly
connected to the CC-Link system.
1: Proper communication is provided.Data from
the sensor amplifi er will be updated.
0: Proper communication is not provided.Data
from the sensor amplifi er will not be updated.

0: In preparation
1: Ready

RX[n] + 3B

RX[n] + 7B

Operating

mode

Device no.

(HEX)

Name

Communication

method

Description

Writing range

S

mall-memor

y mode

1

S

mall-memor

y mode

2

Monitor mode

1

RY[n] + 00
to 03

Integration reset
input
ID 01 to ID 04

*1

Receives integration reset input by assigning
each sensor amplifi er (ID 01 to ID 04) to each
RY.

0: OFF
1: ON

RY[n] + 0F System reserved

-

Unusable

RY[n] + 10
to 13

Flow rate hold
reset input
ID 01 to ID 04

*1

Receives fl ow rate hold reset input by
assigning each sensor amplifi er (ID 01 to ID
04) to each RY.

0: OFF
1: ON

RY[n] + 1F System reserved

-

Unusable

RY[n] + 20
to 23

Zero adjustment
input
ID 01 to ID 04

*1

Receives zero adjustment input by assigning
each sensor amplifi er (ID 01 to ID 04) to each
RY.

0: OFF
1: ON

RX[n] + 2F System reserved

-

Unusable

RY[n] + 30
to 33

Temperature
hold reset input
ID 01 to ID 04

*1

Receives temperature hold reset input by
assigning each sensor amplifi er (ID 01 to ID
04) to each RY.

0: OFF
1: ON

RX[n] + 3F

System reserved

-

Unusable