2 device maps, Co mm u ni c a ting w ith t he fd -s s er ie s – KEYENCE DL-CL1 User Manual

Page 41

Advertising
background image

3-2 Device Maps

3-13

3

Co
mm

u

ni

c

a

ting
w

ith t
he FD

-S

s

er

ie

s

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -

Operating

mode

Device no.

(HEX)

Name

Communication

method

Description

Writing

range

Monitor mode

2

Full mode

1

Full mode

2

RY[n] + 53

Current Value
Update Request

-

Used when locking data update of current
value. This may be used to obtain the current
values of multiple sensor amplifi ers at the
same timing.
The current value is locked while the update
request is held. The update lock state can
be checked by the current value update lock
state (RX[n] + 53).

0: Do not lock
update
1: Request
update lock

RY[n] + 54
to 5F

System reserved

-

Unusable

RY[n] + 60
to 63

(Not used)

-

-

-

RY[n] + 6F (Not used)

-

-

-

RY[n] + 70
to 73

Request to rewrite
instantaneous fl ow
rate setting-1 (P1)
ID 01 to ID 04

*3

Used when rewriting a setting value.
This is input when requesting to rewrite the
instantaneous fl ow rate setting value 1 (P1) of
each sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 04) to each RY.

0->1:
Request to
rewrite

RY[n] + 7F

Clear instantaneous
fl ow rate setting-1
(P1) rewrite error

*3

Used when rewriting a setting value.
This is input when clearing an instantaneous
fl ow rate setting-1 (P1) rewrite error.

0->1: Clear
error

RY[n] + 80
to 83

Request to rewrite
instantaneous fl ow
rate setting-2 (P2)
ID 01 to ID 04

*3

Used when rewriting a setting value.
This is input when requesting to rewrite the
instantaneous fl ow rate setting value 2 (P2) of
each sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 04) to each RY.

0->1:
Request to
rewrite

RY[n] + 8F

Clear instantaneous
fl ow rate setting-2
(P2) rewrite error

*3

Used when rewriting a setting value.
This is input when clearing an instantaneous
fl ow rate setting-2 (P2) rewrite error.

0->1: Clear
error

RY[n] + 90
to 93

Request to rewrite
temperature upper
limit setting
ID 01 to ID 04

*3

Used when rewriting a setting value.
This is input when requesting to rewrite the
temperature upper limit setting value of each
sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 04) to each RY.

0->1:
Request to
rewrite

RY[n] + 9F

Clear temperature
upper limit setting
rewrite error

*3

Used when rewriting a setting value.
This is input when clearing a temperature
upper limit setting-value rewrite error.

0->1: Clear
error

RY[n] + A0
to A3

Request to rewrite
temperature lower
limit setting
ID 01 to ID 04

*3

Used when rewriting a setting value.
This is input when requesting to rewrite the
temperature lower limit setting value of each
sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 04) to each RY.

0->1:
Request to
rewrite

RY[n] + AF

Clear temperature
lower limit setting
rewrite error

*3

Used when rewriting a setting value. This is
input when clearing a temperature lower limit
setting-value rewrite error.

0->1: Clear
error

RY[n] + B0
to B3

Request to rewrite
integrated fl ow
quantity setting-1
ID 01 to ID 0 4

*3

Used when rewriting a setting value.
This is input when requesting to rewrite the
integrated fl ow quantity setting value 1 of
each sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 04) to each RY.

0->1:
Request to
rewrite

RY[n] + BF

Clear integrated
fl ow quantity
setting-1 rewrite
error

*3

Used when rewriting a setting value.
This is input when clearing an integrated fl ow
quantity setting-1 rewrite error.

0->1: Clear
error

RY[n] + C0
to EF

System reserved

-

Unusable

Advertising